15.4.3 Data/Stop
The data size and stop bits of the equipment connected to this port. These
settings determine the number of bits transmitted per ASCII character. The data
size and stop bits you specify depend on the configuration of your equipment.
For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data
bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.
NOTE: When connecting a computer running a terminal emulation program, you
should set your equipment to NO PARITY.
15.4.4 Handshaking
This setting controls handshaking. You can select XON/XOFF or Disabled for this
setting.
Disabled (No Handshaking)
D
If handshaking is disabled, the UPS transmits and receives data via the serial port,
ignoring all inputs from handshaking lines.
XON/XOFF
D
If handshaking is enabled, the UPS uses special characters (XON and XOFF) to
handshake with the host terminal. The XON character is defined to be ASCII
value 11 hex, and the XOFF character is defined to be ASCII value 13 hex.
Upon reception of an XOFF command, the UPS halts transmission until an XON
command is received. In the same way, if the terminal receives an XOFF
command, the UPS expects the terminal to halt transmission until the UPS
sends an XON command.
15.4.5 Save
Set to YES to save any changes to configuration settings upon exit from the Setup
screen. Set to NO if you do not want to save any changes.

15.4.6 Default Settings

The following are the default configuration settings for the serial communications
ports:
Port 1
Port 2
Each communications port on the UPS operates in one of five modes which you
select when configuring the port using the Setup Port screen.
15--6
Remote Monitor
300 baud
Terminal
9600 baud 8/1 Handshaking Disabled
8/1 Handshaking Disabled
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101