Power Supply Wiring; Compobus/S Transmission Line Wiring - Omron SRM1(-V2) Operation Manual

Compobus/s controller
Hide thumbs Also See for SRM1(-V2):
Table of Contents

Advertisement

Wiring and Connections

3-4-2 Power Supply Wiring

Applicable Power Supply
Wiring Connections

3-4-3 CompoBus/S Transmission Line Wiring

Applicable Cable
Use a power supply that conforms to specifications of at least 24 VDC and 3.5 W.
OMRON's S82K-00724 is recommended (input: 100 VAC; output: 24 VDC,
7.5 W).
Note The above power supply is for a case where the CompoBus/S Slave is sepa-
rated from the power supply. Refer to the CompoBus/S Operation Manual
(W266) when supplying power to the whole system including the Slave.
Wire the power supply as shown in the following diagram.
Note Be sure to ground the ground terminal of the power supply.
Be sure to use the specified cable, and do not mix flat cable and VCTF cable.
Cable
Special-purpose flat cable
VCTF cable
+
24 VDC
Model number
XBIT-W10
4-conductor flat cable:
0.75 mm
---
2-conductor Vinyl-clad
VCTF JIS C3306
VCTF 0.75x2C
Section
3-4
Specifications