Power Supply Unit Connection; Specifications And Components - Omron SYSMAC LINK C1000H-SLK21-V1 System Manual

Table of Contents

Advertisement

Power Supply Unit Connection

3-2

Power Supply Unit Connection

3-2-1 Specifications and Components

Specifications
20
2. A Communications Board equipped with a Link Interface (C200HW-
COM01/04-EV1) is required when mounting a SYSMAC LINK Unit to a
C200HX, C200HG, or C200HE PC.
SYSMAC LINK Units that are connected with optical fiber cable (the
C1000H-SLK11 and C200HW-SLK13/14) can be connected to an Auxiliary
Power Supply Unit to provide backup power. By connecting the Unit to an
Auxiliary Power Supply Unit, the entire system won't go down if the Unit fails
for some reason.
The table below shows which Power Supply Units can be connected to the
SYSMAC LINK Units.
SYSMAC LINK Unit
C1000H-SLK11
C200HW-SLK13/14
The following specifications apply to both the C1000H-APS01 and
C200H-APS03.
Item
Power supply voltage
Acceptable voltage range
Power consumption
Weight
Other
Corresponding Power Supply
C1000H-APS01
C200H-APS03
Specification
100 to 120 VAC or 200 to 240 VAC (switchable)
85 to 132 VAC or 170 to 264 VAC
40 VA max.
0.5 kg max.
Conform to C-series specifications
Section 3-2