Digital Input/Digital Output/Analog Output - Honeywell HC900 Installation And User Manual

Honeywell hc900 hybrid controller installation and user guide
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output

Digital Input/Digital Output/Analog Output

The DI/DO/AO-RTP is for use with the following modules:
4-point Analog Output
16-point Contact Digital Input
16-point DC Digital Input
16-point AC Digital Input
16-point DC Digital Output
8-point AC Digital Output
4 Point Analog Output
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
Connect desired cable to AO module at controller. Choose from:
900RTC-L010
900RTC-L025
900RTC-L050
Install AO module label onto the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
2
Mount RTP to DIN rail.
Latch to rail. See page 205.
Connect cable to RTP
3
Set/verify jumper positions as shown for use with an analog output module.
SW1 is not used. Module RIUP is not affected by using the RTP.
See page 203 for RTP internal schematic.
194
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
HC900 Hybrid Controller Installation and User Guide
See page
194
195
197
198
200
201
Action
Jumper open
Jumper closed
Revision 5
9/03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents