Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
16 Point DC Digital Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
Connect desired cable to 16 point DC DI module at controller. Choose from:
900RTC-L010
900RTC-L025
900RTC-L050
Install DC DI module label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
2
Mount RTP to DIN rail.
Latch to rail. See page 205.
Connect cable to RTP
3
Set/verify jumper positions as shown for the 16 point digital input module.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. Please see page 62 for more details.
See page 203 for RTP internal schematic.
Revision 5
9/03
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
HC900 Hybrid Controller Installation and User Guide
Action
Jumper open
Jumper closed
197