Diagnostics and Troubleshooting - User Interface
Table 27 - Controller Module Diagnostics
OI Screen
OI Screen
Item
Item Value
RACK 1
GOOD
VIRTUAL
CONNECT 1 – 5
APPLICATION
ERROR
PEER PORT
GOOD
APPLICATION
ERROR
NETWORK
SETUP
ERROR
NO IP
ADDRESS
HARDWARE
FAILURE
132
Number of
Possible Cause
LED
Strobes
N/A
N/A
10
At least 1 response to
a host resulted in an
exception code
N/A
N/A
10
One of the peer
connection's
application error count
is non-zero
10
Controller/network
names determined on
network are illegal
10
DHCP and IP address
are not configured
10
Ethernet port tests
failed during power-
up.
HC900 Hybrid Controller Installation and User Guide
Control File Action
N/A
1. Rack 1 monitor block's
COMPORT DIAG is set
to WARNING.
2. Rack 1 monitor block's
RACK OK pin is turned
off.
3. ASYS block's HW OK
pin is turned off.
N/A
1. Rack 1 monitor block's
COMPORT DIAG is set
to WARNING.
2. Rack 1 monitor block's
RACK OK pin is turned
off.
3. ASYS block's HW OK
pin is turned off.
1. Rack 1 monitor block's
COMPORT DIAG is set
to FAILED.
2. Rack 1 monitor block's
RACK OK pin is turned
off.
3. ASYS block's HW OK
pin is turned off.
SEE NETWORK SETUP
ERROR
SEE NETWORK SETUP
ERROR
User Action
N/A
At host, determine
which message is
causing the exception
code and fix.
N/A
At host, determine
which message is
causing the exception
code and fix.
Correct the setup
problem.
Enter an IP address.
Replace CPU module
Revision 5
9/03