Specifications - AC Input Module

AC Input Module

Feature
Inputs
Input voltage range
Peak voltage
AC frequency
Isolation
ON voltage level
OFF voltage level
Input Impedance
Input current
Minimum On current
Maximum Off current
Base power required
Response Time
Software filtering

Features Common to all Output Modules

Feature
Micro Controller
Hardware/software keying
Output Diagnostic
Status indicator
LED status indicators
166
2 isolated groups of 8 inputs each
80 to 240 Vac
264 Vac
47 to 63 Hz
2 groups of 8 inputs/group; dielectric strength between groups: 500 Vdc (350
Vac)
75 Vac minimum
20 Vac maximum
48 K ohms
1 mA @ 120 Vac, 60 Hz; 2 mA @ 230Vac, 50 Hz
5 mA
2 mA
230 mA maximum for 5VDC (no 24VDC power)
OFF to ON: 34 ms maximum
ON to OFF: 50 ms maximum
Specific to 50/60 Hz line frequency
Atmel 8515 RISC processor
8k Flash PROM
Key matches module to terminal block connector, ensuring correct board
replacement
Checks output driver ICs
Tri-color LED:
Green - Good
Yellow - at least one output is Forced
Red - Fault
Via light pipes at front of card for each digital output point green indicates On,
logic side
HC900 Hybrid Controller Installation and User Guide
Description
Description
Revision 5
9/03