Communications Installation - Connecting the HC900 Controller to a PC with the Hybrid Control Designer Software

Modem configuration

Before connecting a modem to the controller's RS-232 port (marked "CONFIGURATION"), the modem
must be configured with the following settings:
Baud Rate = 9600, 19200, or 38400 (Must match Baud Rate configured in HC900 Controller)
Parity = None
1 stop bit
8 data bits
No handshaking
Ignore DTR
Suppress result codes
Suppress echo
Auto answer
Disable command recognition (only necessary if the modem has this capability)
Some of these settings may be settable via switches. Others may require command strings to be written to
the modem using a PC terminal program such as Hyperterminal. You will need to refer to your modem's
documentation to make this determination. Those settings that are configured using command strings must
be saved to the modem's non-volatile RAM (NVRAM), and the NVRAM must be configured as the profile
that gets loaded when the modem is powered up.
Most modems are equipped with auto-recognition to set the baud rate, parity, stop bits, and data bits. If
your modem has no means of setting these using switches, then most likely it is equipped with auto-
recognition. To configure the port settings of a modem with auto recognition, do the following:
Step
1
Connect the modem to a PC.
2
Power up the modem.
3
Start up a PC terminal program such as Hyperterminal.
4
Configure the PC COM Port for 9600, 19200, or 38400 baud (must match baud rate configured
in the HC900 Controller), no parity, 1 stop bit, and 8 data bits.
5
Establish communications with the modem. A common way of doing this is simply entering the
AT E1 Q0 command and seeing if the modem responds with OK.
Once you establish communication to the modem, its port settings are configured.
6
Save the port settings to the profile that gets loaded on power-up.