Manual reset value

Sets the required manipulated variable to remove offset during stabilization of P or
PD control.
Function
Setting Range
0.0 to 100.0
Comment
Hysteresis (heat)
Hysteresis (cool)
Sets the hysteresis for ensuring stable operation at ON/OFF switching.
In standard control, use the "hysteresis (heat)" parameter. The "hysteresis (cool)"
parameter cannot be used.
Function
In heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the "hysteresis (heat)" parameter to set the heating side hysteresis,
and use the "hysteresis (cool)" parameter to set the cooling side hysteresis.
Parameter
Hysteresis (heat)
Hysteresis (cool)
Comment
F Related article
4.1 Selecting the Control Method (page 4-3)
F Related parameters
See
"Control output 1 assignment" "Control output 2 assignment" (setup mode)
"PID / ON/OFF" (expansion mode)
Conditions of Use
The control must be standard control,
advanced PID control, ST must be set to
OFF, and the "integral time" parameter
must be set to "0".
Unit
Default
%
50.0
Conditions of Use
The control system must be ON/OFF con-
trol.
Unit
Setting Range
0.01 to 99.99
%FS
0.01 to 99.99
%FS
Level 1 Mode
Default
0.10
0.10
5--13