The parameters in this mode can be used only when the "security" parameter (pro-
tect mode) is set to "0" to "3".
This mode contains the main parameters for adjusting control. These parameters
include parameters for executing AT (auto-tuning), setting the alarm values, setting
the control period, and setting PID parameters.
To select this mode when in the levels 0 and 2, setup, expansion, option and calibra-
tion modes, press the
menu display. If you select [
controller enters the level 1 mode.
To select parameters in this mode, press the
use the
or
keys.
The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol
key for 1 second minimum. The display changes to the
] then press the
Parameter Name
AT Execute/Cancel
Set point 0
Set point 1
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heat)
Hysteresis (cool)
Control period (heat)
Control period (cool)
Level 1 Mode
key for 1 second minimum, the
key. To change parameter settings,
Page
5-10
5-10
5-10
5-11
5-11
5-11
5-11
5-11
5-11
5-12
5-12
5-13
5-13
5-13
5-14
5-14
5--9