Omron E5CK User Manual page 69

Digital controller
Hide thumbs Also See for E5CK:
Table of Contents

Advertisement

CHAPTER 5 PARAMETERS
Level 1 Mode
AT Execute/Cancel
Selects the limit cycle of MV change width (40% or 100%) for execution. After AT
execution, the "PID" and the "LBA detection time" (LBA: Loop Break Alarm) param-
eters are set automatically.
Function
During heating and cooling control, only 100%AT can be executed.
When this parameter is selected, the setting becomes [
To execute 40%AT, select [
execution of auto-tuning, the AT LED flashes. However, note that during heating and
Example
cooling control, [
of use
When AT execution ends, the parameter setting automatically returns to [
F Related article
3.7 Adjusting Control Operation (page 3-13)
F Related parameters
See
"Run/Stop" (level 0 mode)
"Proportional band" "Integral time" "Derivative time" (level 1 mode)
"LBA detection time" (level 2 mode)
Set point 0
Set point 1
When event input is OFF, the "set point 0" parameter is used, and when ON, the "set
point 1" parameter is used.
When the "set point" parameter has been changed, the setting of whichever is
Function
selected in event input, "set point 0" or "set point 1", is linked and changed.
The decimal point position is dependent on the selected sensor during temperature
input and on the results of scaling during analog input.
Scaling lower limit to Scaling upper limit
Comment
F Related article
4.3 How to Use Option Functions (page 4-8)
F Related parameters
See
"Multi-SP function" (option mode)
"Set point" (level 0 mode)
"Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" (setup
mode)
5--10
], and to execute 100%AT, select [
] is not displayed.
Setting Range
Conditions of Use
The controller must be in operation, con-
trol must be advanced PID control, and ST
must be set to OFF.
].
Conditions of Use
The multi-SP function must be in
operation.
Unit
Default
EU
0
]. During
].