CHAPTER 5 PARAMETERS
Level 1 Mode
Control period (heat)
Control period (cool)
Sets the pulse output period. Set the control period taking the control characteristics
and life expectancy of the controller into consideration.
In standard control, use the "control period (heat)" parameter. The "control period
Function
(cool)" parameter cannot be used.
In heating and cooling control, the control period can be set independently for heat-
ing and cooling. Use the "control period (heat)" parameter to set the heating side con-
trol period, and use the "contrlo period (cool)" parameter to set the cooling side con-
trol period.
Comment
F Related article
3.3 Setting Output Specifications (page 3-5)
F Related parameters
See
"Control output 1 assignment" "Control output 2 assignment" (setup mode)
5--14
Parameter
Setting Range
Control period (heat)
Control period (cool)
Conditions of Use
Relay or voltage output must be set as the
outputs, and the control must be set to
advanced PID control.
Unit
1 to 99
Second
1 to 99
Second
Default
20
20