Observe allgoverning c odesandordinances when
grounding. Intheabsence ofthesecodes or
ordinances observe National Electrical Code ANSI/
NFPANo.70current i ssue. S eethefollowing
information i nthissection, " Step
6: Electrical
Requirements,
Connection & Grounding", for
grounding method.
Electrical wiring diagrams and schematics have been
placed in the kick panel area of the range for access by
a qualified service technician (see Figure 4 on page 9).
The ranges are to be connected to a 240/208 VAC
power supply.
Dual Fuel models must be connected to the power supply
utilizing one of the following methods. For all methods of
connection, the length of the cord or conduit/wiring
must
allow the unit to be slid completely out of the cabinet
without having to unplug or disconnect the unit from the
power supply. Recommended minimum free length of cord
or conduit is 4ft (1.2m). Electrical installations and
grounding must be in accordance with all local codes and
ordinances, and/or the National Electric Code, as
applicable.
o0
03
C
1_3_J
T
I
/
/
/
I
/'
ll.,
_rminal B5 :k
Cover
u
c----,,
Figure 11: Location of Terminal Block
PERMANENT
CONNECTION/HARD
WIRING) --
Units may be hard wired to the power supply. The installer
must provide approved flexible aluminum conduit, 3/4"
(19mm) trade size, maximum 6ft (1.8m)long.
Locate the
terminal block on the rear of the unit and remove cover
(refer to Figure 11). The conduit must be installed to the
terminal block using an approved conduit connector. The
free end of the conduit must be connected to a terminal
block provided in the electrical supply zone, as shown in
Figure 3a on page 7.
Mount a strain relief (not provided) into the 1" (25.4mm)
diameter hole located below the terminal block (see
Figure 12). Wiring for the unit is to be brought into the
terminal block through the conduit and through the strain
relief. The ends of the wiring must have 1/4" (6mm) faston
closed-loop lugs attached, preferably soldered in place.
Make the connections to the terminal block provided.
If aluminum supply wiring exists in the installation, splice
the aluminum house wiring with appropriate-thickness
gauge copper wire for adapting to the range, using special
connectors designed and certified for joining copper and
aluminum wire. Follow the connector manufacturer's
recommended
installation procedure.
, WARNING:
Improper connection of aluminum house wiring can
result in a fire or shock hazard. Use only connectors
designed and certified for connecting to aluminum wire.
Installer -- show the owner the location of the circuit
breaker. Mark it for easy reference.
Terminal Block
|
|
Strair_ Relief
\
Figure 12: Strain Relief Location
English 15