OneWireless™ Series User Manual
3.4

Configuration

The WCX valve position sensor contains a mechanical interface compatible for connecting to the
OneWireless network. An operator uses the wireless builder application to configure blocks, to change
operating parameters, and to create linkages between blocks that make up the sensor's configuration.
These changes are written to the sensor when it is authenticated by a security key. See Section 5.
If this is the first WCX Series sensor installed on your OneWireless network you will need to update the
DD files in wireless builder in order to properly communicate with the WCX Series sensor. These files are
available on the CD that was included with the sensor. If this is not the first device, please proceed to
section 3.5.
Table 2. Updating DD Files
Step
Action
1
Copy the folder "WCX DD files" from the provided WCX Series documentation CD to a known location on
the host PC. The files may also be downloaded from the web at:
http://hpsweb.honeywell.com/Cultures/en-US/Products/Wireless/
xyr6000wireless/XYR6000ValvePositioner/default.htm
2
Go to File->New->Type->Wireless Device and then browse to the path of the WCX DD Files.
3
Select the device that appears and then click OK. This creates a new device type in Wireless Builder.
3.5

Connecting to Network

For instructions on how to use an Authentication Device to connect the WCX Series sensor to the
OneWireless network, see Section 5.6.
Table 3. Connecting and Commissioning the Sensor
Step
Action
1
Connecting device to OneWireless network
1.1
If applicable, remove two T-15 TORX screws and cover lock clamp.
1.2
Using a screwdriver or other tool across the two tabs of the cover, unscrew and remove the cover.
1.3
Remove the battery insulator. Reseat the batteries if necessary and verify that the LCD display reads "NO
KEY"
1.4
After transmitter restarts, use authentication device to transmit key and connect transmitter.
1.5
Device will go through discovery mode, then secure itself to OneWireless network. After this phase, the
WCX sensor will appear in Wireless Builder as an uncommissioned device.
2
Commissioning device in Wireless Builder
2.1
Right click on the WCX device block and select commission device. If a prompt appears requesting DD
files, then exit this screen and follow the instructions in Table 2.
2.2
Enter a new tag name if desired. Click Next and then click Finish.
2.3
Right click on the device tranducer block and then select Activate -> Selected Device.
2.4
Wait a few minutes and then the device will be active and transmitting data.
50040849
Issue 3