OneWireless™ Series User Manual

Restoring Factory Settings

Prior to scaling or converting the engineering units it is necessary to confirm the range values of the device
are set at the factory defaults. To return the range settings to the factory defaults, follow the instructions in
Table 5.
Table 6. Restoring Factory Default Range Settings
Step
In Wireless Builder in the range tab, verify the readings for EU@100 % and EU@0 %. The
1
factory settings are EU@100 % = 314 and EU@0% = -4%. If these have been changed, then
they need to be reset to these values.
In Wireless Builder, in the Main tab, set unit to OOS. In the Range tab, input these two values
2
in the appropriate fields. After inputting the new EU Values, in the Main tab, set unit to AUTO.
There are options in Wireless Builder to restore calibration and clear calibration. Do not use the Cal
Clear or Cal Restore options as this may result in incorrect sensor output readings and require the unit to
be returned for factory calibration.
3.6. Setting the Range and Engineering Units
Action
50040849
Issue 3