Input Circuit; E.4 Power Supply Conditions; E.4.1 Input Circuit - Fujitsu SPARC Enterprise M5000 Service Manual

Fujitsu server user manual
Hide thumbs Also See for SPARC Enterprise M5000:
Table of Contents

Advertisement

UPS Interface Signals
TABLE E-1
Signal Name
Definitions
*BPS/*UALM
Signal indicates faulty UPS conditions
*BTL
Signal provides a warning of a low battery level
and a pending UPS failure.
*ACOFF
Signal indicates power failure at the commercial
AC supply connector to the UPS
SG
Signal ground
ER
Signal indicates the main unit is running
(Equipment Ready)
ON:Indicates contacts are closed
OFF: Indicates contacts are open
Note1: Use a UPS capable of normal battery power supply operation for at least 10 to 60 seconds after this signal is turned on.
Note2: Use a UPS capable of normal battery power supply output without turning on the *ACOFF in an instantaneous commercial AC
power failure lasting two seconds or less.
E.4
Power Supply Conditions
TABLE E-2
E.4.1

Input circuit

TABLE E-2
Signal Name
*BPS/*UALM
*BTL
*ACOFF
Limit the signal-line chatter period to 1ms or less.
and
list the electrical specifications for the UPS interface.
TABLE E-3
Electrical Specifications
Input Conditions
No voltage relay contact
Contact rating DC 12 V, 10 mA or more (maximum 0.5A)
Use of metallic contact, or lead relay is recommended.
Pin Number
Remarks
6
Normal: OFF
Failure: ON
7
Normal: OFF
Warning: ON
(Note1)
9
Normal: OFF
Power failure: ON
(Note2)
5
1
Do not connect to ER
signal pin.
Appendix E
UPS Controller
E-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sparc enterprise m4000

Table of Contents