Object And Diagnostic Data Points With Corresponding Chiller Models - Trane R Series Installation, Operation And Maintenance Manual

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Installation - Electrical
Device Address Binding
Device Address Binding
Static Device Binding Supported
Networking Options
Networking Descriptions
Annex H, BACnet Tunneling
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD Support Registrations by Foreign
Devices?
Router
Character Sets
Indicates support for multiple characters sets, but does not
imply that all character sets are supported simultaneously.
Maximum supported string length is 64 bytes (any
character set).
Character Set Descriptions
ANSI X3.4
Table 47.
Analog Output
Object Identifier
Object Name
Analog Output 1
Chilled Water Setpoint
Analog Output 2
Current Limit Setpoint
Analog Output 4
Hot Water Setpoint
Table 48. Analog Input
Object
Identifier
Object Name
Analog Input, 1
Active Cool/Heat Setpoint Temperature
Analog Input, 2
Active Current Limit Setpoint
Analog Input, 5
Actual Running Capacity
Analog Input, 7
Suction Pressure- Ckt 1
Analog Input, 10
Suction Pressure- Ckt 2
Evaporator Saturated Refrigerant
Analog Input, 12
Temperature- Ckt 1
Evaporator Saturated Refrigerant
Analog Input, 14
Temperature- Ckt 2
Analog Input, 16
Condenser Refrigerant Pressure- Ckt 1
Analog Input, 18
Condenser Refrigerant Pressure- Ckt 2
Condenser Saturated Refrigerant
Analog Input, 20
Temperature- Ckt 1
Condenser Saturated Refrigerant
Analog Input, 22
Temperature- Ckt 2
Analog Input, 24
Unit Power Consumption
98
Supported?
ü
Supported
Option
Supported
ü
Description
Desired leaving water
temperature if chiller is in cooling
mode.
Sets the maximum capacity that
the chiller can use.
Desired leaving water
temperature if chiller is in heating
mode.
Description
Active chiller water or hot water setpoint.
Active capacity current limit setpoint.
Level of capacity that the chiller is currently
running at.
Circuit 1 suction pressure.
Circuit 2 suction pressure.
Circuit 2 evaporator refrigerant temperature.
Circuit 2 evaporator refrigerant temperature.
Circuit 1 condenser refrigerant pressure.
Circuit 2 condenser refrigerant pressure.
Circuit 1 condenser refrigerant temperature.
Circuit 2 condenser refrigerant temperature.
The power being consumed by the chiller.
IBM/Microsoft DBCS
ISO 10646 (UCS-4)
ISO 10646 (UCS2)
ISO 8859-1
JIS C 6226
Object and Diagnostic Data Points with
Corresponding Chiller Models
For quick reference, the following tables are listed two
different ways.
Table 47
through
input/output type and sorted by object identifier.These
tables provide the user with the units type for each object
type.
Table 53
is sorted by object name and provides a
complete list of object names, types, values/ranges, and
descriptions. Not all points are available to the user.The
available data points are defined during self-configuration
and are dependent on the type of equipment.
Units
Degrees-Fahrenheit
(64)
Percent (98)
Degrees-Fahrenheit
(64)
ü
ü
Table 52
are listed by
Relinq
Valid Range
Default
0°F to 75°F
44°F
0% to 120%
100%
80°F to 140°F
120°F
Units
Degrees-Fahrenheit (64)
Percent (98)
Percent (98)
PSI
PSI
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
PSI
PSI
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Kilowatts
RTAC-SVX01J-EN