Trane R Series Installation, Operation And Maintenance Manual page 151

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Diagnostics
Table 66. Starter diagnostics (continued)
Diagnostic Name
Affects
and Source
Target Severity Persistence
Starter Contactor
Interrupt Failure -
Chiller
Compressor 2A
Starter Contactor
Interrupt Failure -
Chiller
Compressor 1A
Starter Contactor
Interrupt Failure -
Chiller
Compressor 1B
Starter Contactor
Interrupt Failure -
Chiller
Compressor 2B
Starter Did Not
Transition -
Cprsr
Compressor 1A
Starter Did Not
Transition -
Cprsr
Compressor 1B
Starter Did Not
Transition -
Cprsr
Compressor 2A
Starter Did Not
Transition -
Cprsr
Compressor 2B
RTAC-SVX01J-EN
Active
Modes
[Inactive
Modes]
Starter
Contactor
Special
Latch
Energized
Mode
[Starter
Contactor
Energized]
Starter
Contactor
Special
Latch
Energized
Mode
[Starter
Contactor
Energized]
Starter
Contactor
Special
Latch
Energized
Mode
[Starter
Contactor
Energized]
Starter
Contactor
Special
Latch
Energized
Mode
[Starter
Contactor
Energized]
On the first
Immediate
Latch
check after
transition.
On the first
Immediate
Latch
check after
transition.
On the first
Immediate
Latch
check after
transition.
On the first
Immediate
Latch
check after
transition.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
not
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
not
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
not
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
Detected compressor currents greater than 10% RLA on any or all
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On
detection and until the controller is manually reset: generate
not
diagnostic, energize the appropriate alarm relay, continue to
energize the Evap Pump Output, continue to command the
affected compressor off, fully unload the effected compressor and
command a normal stop to all other compressors. For as long as
current continues, perform liquid level and fan control on the
circuit effected.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must
hold time from the Starter Module transition command is 1
second. The Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds. This diagnostic is active
only for Y-Delta, Auto-Transformer, Primary Reactor, and X-Line
Starters.
Criteria
Reset
Level
Local
Local
Local
Local
Local
Local
Local
Local
151