Trane R Series Installation, Operation And Maintenance Manual page 149

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Diagnostics
Table 66. Starter diagnostics (continued)
Diagnostic Name
Affects
and Source
Target Severity Persistence
Phase Loss -
Cprsr
Compressor 1B
Phase Loss -
Cprsr
Compressor 2A
Phase Loss -
Cprsr
Compressor 2B
Phase Reversal -
Cprsr
Compressor 1A
Phase Reversal -
Cprsr
Compressor 1B
Phase Reversal -
Cprsr
Compressor 2A
Phase Reversal -
Cprsr
Compressor 2B
RTAC-SVX01J-EN
Active
Modes
[Inactive
Modes]
Sequence
Immediate
Latch
and Run
modes
Sequence
Immediate
Latch
and Run
modes
Sequence
Immediate
Latch
and Run
modes
Compressor
energized to
transition
Immediate
Latch
command
[All Other
Times]
Compressor
energized to
transition
Immediate
Latch
command
[All Other
Times]
Compressor
energized to
transition
Immediate
Latch
command
[All Other
Times]
Compressor
energized to
transition
Immediate
Latch
command
[All Other
Times]
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
Start
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trippoint is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current xformer inputs.
Logic will detect and trip in a maximum of 0.3 second from
compressor start
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
Start
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trippoint is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current xformer inputs.
Logic will detect and trip in a maximum of 0.3 second from
compressor start
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
Start
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trippoint is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current xformer inputs.
Logic will detect and trip in a maximum of 0.3 second from
compressor start
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of .3 second from compressor start.
Criteria
Reset
Level
Local
Local
Local
Local
Local
Local
Local
149