Setpoint Screen - Trane R Series Installation, Operation And Maintenance Manual

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Controls Interface
Table 59. Refrigerant screen
Description
Cond Rfgt Pressure Ckt1/Ckt2
Sat Cond Rfgt Temp Ckt1/Ckt2
Evap Rfgt Pressure Ckt1/Ckt2
Sat Evap Rfgt Temp Ckt1/Ckt2
Evap Approach Temp Ckt1/Ckt2 X.X
Rfgt Liquid Level Ckt1/Ckt2

Setpoint Screen

The setpoint screen is a two-part screen. Screen 1 lists all
setpoints available to change along with their current
value. The operator selects a setpoint to change by
touching either the verbal description or setpoint value.
Doing this causes the screen to switch to Screen 2.
In Screen 1 the language setpoint will always be the last
setpoint in the list. This will facilitate language changes by
placing that control in a standard position across all
CH.530 product lines.
Screen 2 displays the current value of the chosen setpoint
in the upper ½ of the display. It is displayed in a
changeable format consistent with its type. Binary
setpoints are considered to be simple two state
enumeration and will use radio buttons. Analog setpoints
are displayed as spin buttons. The lower half of the screen
is reserved for help screens.
Table 61
Setpoint options/conditions displayed
Option
Ice Building
Cprsr Pumpdown
1
EXV Ckt Open
(For Authorized Service Use Only
Notes:
1 Pumpdown procedure are discussed in Maintenance section 10.
2 Used for liquid level control or to recover from pumpdown
116
Resolution
Units
X.X
Pressure
X.X
F / C
X.X
Pressure
X.X
F / C
F / C
X.X
Height
Condition(s)
Explanation
Enable/Disable
If feature is installed, operation can be initiated or stopped
Avail
Pumpdown is allowed: only with unit in Stop or when circuit is locked out
Not Avail
Pumpdown is not allowed because unit is operating or pumpdown has been completed
Pumpdown
State is displayed while pumpdown is in progress
Indicates EXV is closed but can be opened manually since unit is in Stop or circuit is
Avail
locked out
2
)
Not Avail
EXV is closed but cannot be opened manually since unit is operating
Table 60. Setpoint screen
Description
Auto Local or Remote
Front Panel Chilled Water
Setpoint
Front Panel Current Limit
Setpoint
Differential to Start
Differential to Stop
Condenser Limit Setpoint
Low Ambient Lockout Setpoint
Low Ambient Lockout
Ice Build
Front Panel Ice Termination
Setpoint
Comp 1A Pumpdown
Comp 1B Pumpdown
Comp 2A Pumpdown
Comp 2B Pumpdown
EXV Ckt 1 Open
EXV Ckt 2 Open
Front Panel Ckt 1 Lockout
Front Panel Ckt 2 Lockout
Ext Chilled Water Setpoint
Ext Current Limit Setpoint
Date Format
Date
Time Format
Time of Day
Keypad/Display Lockout
Display Units
Pressure Units
Language Selection
Resolution or
Text
Units
Remote/Local
Text
X.X
F / C
XXX
% RLA
X.X
Temperature
X.X
Temperature
Enable/Disable
Text
X.X
Temperature
Enable/Disable
Text
Enable/Disable
Text
X.X
Temperature
Pumpdown/Abort Text
Pumpdown/Abort Text
Pumpdown/Abort Text
Pumpdown/Abort Text
Auto/Open
Text
Auto/Open
Text
Locked Out/Not
Text
Locked Out
Locked Out/Not
Text
Locked Out
X.X
F / C
XXX
% RLA
mmm dd yyyy, dd
Text
mm yyyy
Text
12 hr, 24 hr
Text
Text
Enable/Disable
Text
SI, English
Text
Absolute, Gauge
Text
Downloaded from
Text
TechView
RTAC-SVX01J-EN