Trane R Series Installation, Operation And Maintenance Manual page 102

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Installation - Electrical
Table 52.
Binary Input (continued)
Object
Identifier
Object Name
Binary Input, 5
Condenser Water Flow Status
Binary Input, 6
Maximum Capacity
Binary Input, 7
Head Relief Request
Binary Input, 9
Compressor 1A Running
Binary Input, 10
Compressor 1B Running
Binary Input, 11
Compressor 2A Running
Binary Input, 12
Compressor 2B Running
Evaporator Water Pump
Binary Input, 17
Request
Condenser Water Pump
Binary Input, 19
Request
Binary Input, 20
Noise Reduction Active
Binary Input, 22
Evaporator Water Flow Status
Binary Input, 23
Alarm Present
Binary Input, 24
Shutdown Alarm Present
Binary Input, 25
Last Diagnostic
Table 53.
All Object Types Sorted by Object Name (
Object
(a)
Identifier
Object Name
Analog Output 1
Chilled Water Setpoint
Analog Output 2
Current Limit Setpoint
Analog Output 4
Hot Water Setpoint
Analog Input, 1
Active Cool/Heat Setpoint Temperature
Analog Input, 2
Active Current Limit Setpoint
Analog Input, 5
Actual Running Capacity
Analog Input, 7
Suction Pressure- Ckt 1
Analog Input, 10
Suction Pressure- Ckt 2
Analog Input, 12
Evaporator Saturated Refrigerant Temperature- Ckt 1
Analog Input, 14
Evaporator Saturated Refrigerant Temperature- Ckt 2
Analog Input, 16
Condenser Refrigerant Pressure- Ckt 1
Analog Input, 18
Condenser Refrigerant Pressure- Ckt 2
Analog Input, 20
Condenser Saturated Refrigerant Temperature- Ckt 1
Analog Input, 22
Condenser Saturated Refrigerant Temperature- Ckt 2
Analog Input, 24
Unit Power Consumption
Analog Input, 25
Local Atmospheric Pressure
Analog Input, 26
Starts- Compressor 1A
102
Description
Condenser water flow status.
Indicates if all available chiller capacity is being used.
Indicates if the chiller is asking an outside system to
provide more heat rejection from the condenser water
loop.
Indicates if compressor 1A is running.
Indicates if compressor 1B is running.
Indicates if compressor 2A is running.
Indicates if compressor 2B is running.
Indicates a request from the chiller to turn on the
evaporator water pump.
Indicates a request from the chiller to turn on the
condenser water pump.
Indicates if the chiller is in a state where noise is being
reduced.
Indicates if water is flowing through the evaporator.
Indicates if an alarm is active.
Indicates if a shutdown alarm is active.
Indicates last diagnostic for the chiller.
Refer to previous tables for detailed descriptions of objects
Description
Desired leaving water temperature if chiller is in cooling mode.
Sets the maximum capacity that the chiller can use.
Desired leaving water temperature if chiller is in heating mode.
Active chiller water or hot water setpoint.
Active capacity current limit setpoint.
Level of capacity that the chiller is currently running at.
Circuit 1 suction pressure.
Circuit 2 suction pressure.
Circuit 2 evaporator refrigerant temperature.
Circuit 2 evaporator refrigerant temperature.
Circuit 1 condenser refrigerant pressure.
Circuit 2 condenser refrigerant pressure.
Circuit 1 condenser refrigerant temperature.
Circuit 2 condenser refrigerant temperature.
The power being consumed by the chiller.
Local atmospheric pressure.
Number of starts for compressor 1A.
Object States
Inactive = No Flow
Active = Flow
Inactive = Off
Active = On
Inactive = Off
Active = On
Inactive = Off
Active = Running
Inactive = Off
Active = Running
Inactive = Off
Active = Running
Inactive = Off
Active = Running
Inactive = Off
Active = On
Inactive = Off
Active = On
Inactive = Off
Active = On
Inactive = No Flow
Active = Flow
Inactive = No Alarm
Active = Alarm
Inactive = No Alarm
Active = None
Inactive = Off
Active = On
)
RTAC-SVX01J-EN