Summary of Contents for Trane Sintesis RTAF-SVX002D-EN
Page 1
Installation, Operation, and Maintenance Sintesis™ Air-Cooled Chillers Model RTAF, 500 Tons Middle East Applications Only Supplement to RTAF-SVX001*-EN SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
Page 2
Practices with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to Trane believes that responsible refrigerant practices are servicing the unit. NEVER PERFORM ANY important to the environment, our customers, and the air SWITCHING, DISCONNECTING, OR VOLTAGE conditioning industry.
Page 3
Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
R-134a Refrigerant Charge (ckt 1/ckt 2) lbs (kg) 310.6/323.3 (140.9/146.6) Trane Oil 00311 (bulk)/OIL00315 (1 gal)/OIL00317 (5 gal) Oil Charge (ckt 1/ckt 2) gal (L) 4.33/4.37 (16.4/16.5) (a) Nominal tonnage at 60 Hz. Where there are 2 compressors on a circuit, they are indicated 1A-1B/2A-2B.
Operating Principles Economizer The economizer system's two main components are an electronic expansion valve (EXV) and a brazed plate heat exchanger (BPHE). The liquid flow leaving the condenser is routed through the economizer BPHE. One side is the economizer refrigerant flow and the other side is the evaporator refrigerant flow.
Start-Up and Shutdown Temporary Shutdown And Important: Initial unit commissioning start-up must be performed by Trane or an agent of Trane Restart specifically authorized to perform start-up and warranty of Trane products. Contractor To shut the unit down for a short time, use the following...
Trane assumes no responsibility for equipment failures 3. Close the vents in the evaporator chilled water circuits. which result from untreated or improperly treated 4.
Start-Up and Shutdown Sequence of Operation can be though of as a state chart, with the arrows and arrow text depicting the transitions between states. This section will provide basic information on chiller • The text in the circles is the visible top level operating operation for common events.
Start-Up and Shutdown Power Up Diagram The Power up chart shows the respective TD-7 AdaptiView the last mode before power down was 'Auto', the screens during a power up of the Symbio™ 800 and transition from 'Stopped' to 'Starting' occurs, but it is not display.
Start-Up and Shutdown Power Up to Starting The Power up to starting diagram shows the timing from • Need to cool (differential to start) already exists a power up event to energizing the 1 compressor. The • Oil level is detected immediately shortest allowable time would be under the following The above conditions would allow for a minimum power conditions:...
Start-Up and Shutdown Stopped to Starting The figure below shows the timing from a stopped mode • Evaporator Water flow occurs quickly with pump on to energizing the first compressor. The shortest allowable command time would be under the following conditions: •...
Start-Up and Shutdown Running (Lead Compressor/Circuit Start and Run) The figure below shows a typical start and run sequence for the lead compressor and its circuit. Figure 6. Sequence of operation: running (lead compressor/circuit start nd run) Chiller and Lead Circuit Stage On Enter Exit...
Start-Up and Shutdown Running (Lag Compressor/Circuit Start and Run) The figure below shows a typical start and run sequence for the lag compressor and its circuit. Figure 7. Sequence of operation: running (lag compressor/circuit start nd run) All Compressors Running Chiller and Both Circuit Enter Exit...
Start-Up and Shutdown Satisfied Setpoint The figure below shows the normal transition from Running to shutting down due to the Evap Leaving water temp falling below the differential to stop setpoint. Figure 8. Sequence of events: satisfied setpoint Normal Pumpdown Termination Differential to Stop is Met Criteria is Met for Last Circuit 8 1 / / 0/...
Start-Up and Shutdown Unloading Unstaging The figure below shows the normal transition from full load to minimum load while the chiller is running. Figure 9. Sequence of events: Unloading unstaging All Compressors Running At Less Than Max Capacity Normal Pumpdown Termination * * * StageOff Setpoint Met Criteria is Met for Last Circuit...
Start-Up and Shutdown Normal Shutdown to Stopped or Run Inhibit The figure below shows the Transition from Running on the top attempt to show the final mode if you enter the through a Normal (friendly) Shutdown. The Dashed lines stop via various inputs. Figure 10.
Start-Up and Shutdown Immediate Shutdown to Stopped or Run Inhibit The figure below shows the transition from Running top attempt to show the final mode if you enter the stop via through an Immediate Shutdown. The dashed lines on the various inputs.
Start-Up and Shutdown Ice Making (Running to Ice Making to Running) The figure below shows the transition from normal cooling to Ice making, back to normal cooling. Figure 12. Sequence of events: ice making (running to ice making to running) Ice Making Command: Evap Leaving Ice Making Command...
Start-Up and Shutdown Ice Making (Auto to Ice Making to Ice Making Complete) The figure below shows the transition from Auto to Ice making, to Ice Making Complete. Figure 13. Sequence of events: ice making (auto to ice making to ice making complete) Ice Making Command: Evap Entering Water 1.
Diagnostics This list includes only those diagnostics unique to Middle Persistence: Defines whether or not the diagnostic and its East application configuration. See Sintesis™ RTAF effects are to be manually reset (Latched), or can be either Installation, Operation, and Maintenance Manual manually or automatically reset when and if the condition RTAF-SVX001*-EN for full unit diagnostics list.
Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors.
Page 28
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.