Trane Sintesis RTAF-SVX002D-EN Installation, Operation And Maintenance Manual

Trane Sintesis RTAF-SVX002D-EN Installation, Operation And Maintenance Manual

Air-cooled chillers, 500 tons

Advertisement

Quick Links

Installation, Operation, and Maintenance
Sintesis™ Air-Cooled Chillers
Model RTAF, 500 Tons
Middle East Applications Only
Supplement to RTAF-SVX001*-EN
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
April 2022
SAFETY WARNING
RTAF-SVX002D-EN

Advertisement

Table of Contents
loading

Summary of Contents for Trane Sintesis RTAF-SVX002D-EN

  • Page 1 Installation, Operation, and Maintenance Sintesis™ Air-Cooled Chillers Model RTAF, 500 Tons Middle East Applications Only Supplement to RTAF-SVX001*-EN SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
  • Page 2 Practices with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to Trane believes that responsible refrigerant practices are servicing the unit. NEVER PERFORM ANY important to the environment, our customers, and the air SWITCHING, DISCONNECTING, OR VOLTAGE conditioning industry.
  • Page 3 Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
  • Page 4: Table Of Contents

    Table of Contents Model Number Descriptions ....5 General Information ..... 6 General Data .
  • Page 5: Model Number Descriptions

    Digit 9 — Manufacturing Percent Capacity and Location Digit 24 — Condenser Fin Programmable Relay Options Trane Commercial Systems, Digit 34 — Energy Meter Pueblo, CO USA Aluminum Microchannel None Digits 10, 11— Design Sequence Digit 25 — Fan Type Digit 35 —...
  • Page 6: General Information

    R-134a Refrigerant Charge (ckt 1/ckt 2) lbs (kg) 310.6/323.3 (140.9/146.6) Trane Oil 00311 (bulk)/OIL00315 (1 gal)/OIL00317 (5 gal) Oil Charge (ckt 1/ckt 2) gal (L) 4.33/4.37 (16.4/16.5) (a) Nominal tonnage at 60 Hz. Where there are 2 compressors on a circuit, they are indicated 1A-1B/2A-2B.
  • Page 7: Operating Principles

    Operating Principles Circuit Schematic Figure 1. Schematic, refrigerant and oil systems — RTAF middle east configuration RTAF-SVX002D-EN...
  • Page 8 Operating Principles Table 2. Legend Description Description Description Screw Compressor Electronic Expansion Valve Pressure Transducer Evaporator Sight Glass High Pressure Relief Valve Air-Cooled Condenser Relief Valve Low Pressure Relief Valve Evaporator Water Inlet Connection Service Valve High Pressure Switch Evaporator Water Outlet Connection Solenoid Valve Temperature Sensor Oil Service Valve...
  • Page 9: Economizer

    Operating Principles Economizer The economizer system's two main components are an electronic expansion valve (EXV) and a brazed plate heat exchanger (BPHE). The liquid flow leaving the condenser is routed through the economizer BPHE. One side is the economizer refrigerant flow and the other side is the evaporator refrigerant flow.
  • Page 10: Start-Up And Shutdown

    Start-Up and Shutdown Temporary Shutdown And Important: Initial unit commissioning start-up must be performed by Trane or an agent of Trane Restart specifically authorized to perform start-up and warranty of Trane products. Contractor To shut the unit down for a short time, use the following...
  • Page 11: Seasonal Unit Start-Up Procedure

    Trane assumes no responsibility for equipment failures 3. Close the vents in the evaporator chilled water circuits. which result from untreated or improperly treated 4.
  • Page 12: Sequence Of Operation

    Start-Up and Shutdown Sequence of Operation can be though of as a state chart, with the arrows and arrow text depicting the transitions between states. This section will provide basic information on chiller • The text in the circles is the visible top level operating operation for common events.
  • Page 13: Power Up Diagram

    Start-Up and Shutdown Power Up Diagram The Power up chart shows the respective TD-7 AdaptiView the last mode before power down was 'Auto', the screens during a power up of the Symbio™ 800 and transition from 'Stopped' to 'Starting' occurs, but it is not display.
  • Page 14: Power Up To Starting

    Start-Up and Shutdown Power Up to Starting The Power up to starting diagram shows the timing from • Need to cool (differential to start) already exists a power up event to energizing the 1 compressor. The • Oil level is detected immediately shortest allowable time would be under the following The above conditions would allow for a minimum power conditions:...
  • Page 15: Stopped To Starting

    Start-Up and Shutdown Stopped to Starting The figure below shows the timing from a stopped mode • Evaporator Water flow occurs quickly with pump on to energizing the first compressor. The shortest allowable command time would be under the following conditions: •...
  • Page 16: Running (Lead Compressor/Circuit Start And Run)

    Start-Up and Shutdown Running (Lead Compressor/Circuit Start and Run) The figure below shows a typical start and run sequence for the lead compressor and its circuit. Figure 6. Sequence of operation: running (lead compressor/circuit start nd run) Chiller and Lead Circuit Stage On Enter Exit...
  • Page 17: Running (Lag Compressor/Circuit Start And Run)

    Start-Up and Shutdown Running (Lag Compressor/Circuit Start and Run) The figure below shows a typical start and run sequence for the lag compressor and its circuit. Figure 7. Sequence of operation: running (lag compressor/circuit start nd run) All Compressors Running Chiller and Both Circuit Enter Exit...
  • Page 18: Satisfied Setpoint

    Start-Up and Shutdown Satisfied Setpoint The figure below shows the normal transition from Running to shutting down due to the Evap Leaving water temp falling below the differential to stop setpoint. Figure 8. Sequence of events: satisfied setpoint Normal Pumpdown Termination Differential to Stop is Met Criteria is Met for Last Circuit 8 1 / / 0/...
  • Page 19: Unloading Unstaging

    Start-Up and Shutdown Unloading Unstaging The figure below shows the normal transition from full load to minimum load while the chiller is running. Figure 9. Sequence of events: Unloading unstaging All Compressors Running At Less Than Max Capacity Normal Pumpdown Termination * * * StageOff Setpoint Met Criteria is Met for Last Circuit...
  • Page 20: Normal Shutdown To Stopped Or Run Inhibit

    Start-Up and Shutdown Normal Shutdown to Stopped or Run Inhibit The figure below shows the Transition from Running on the top attempt to show the final mode if you enter the through a Normal (friendly) Shutdown. The Dashed lines stop via various inputs. Figure 10.
  • Page 21: Immediate Shutdown To Stopped Or Run Inhibit

    Start-Up and Shutdown Immediate Shutdown to Stopped or Run Inhibit The figure below shows the transition from Running top attempt to show the final mode if you enter the stop via through an Immediate Shutdown. The dashed lines on the various inputs.
  • Page 22: Ice Making (Running To Ice Making To Running)

    Start-Up and Shutdown Ice Making (Running to Ice Making to Running) The figure below shows the transition from normal cooling to Ice making, back to normal cooling. Figure 12. Sequence of events: ice making (running to ice making to running) Ice Making Command: Evap Leaving Ice Making Command...
  • Page 23: Ice Making (Auto To Ice Making To Ice Making Complete)

    Start-Up and Shutdown Ice Making (Auto to Ice Making to Ice Making Complete) The figure below shows the transition from Auto to Ice making, to Ice Making Complete. Figure 13. Sequence of events: ice making (auto to ice making to ice making complete) Ice Making Command: Evap Entering Water 1.
  • Page 24: Diagnostics

    Diagnostics This list includes only those diagnostics unique to Middle Persistence: Defines whether or not the diagnostic and its East application configuration. See Sintesis™ RTAF effects are to be manually reset (Latched), or can be either Installation, Operation, and Maintenance Manual manually or automatically reset when and if the condition RTAF-SVX001*-EN for full unit diagnostics list.
  • Page 25: Main Processor Diagnostics

    Diagnostics Main Processor Diagnostics Table 4. Main processor diagnostics Affects Active Modes Reset Diagnostic Name Severity Persistence Criteria Target [Inactive Modes] Level Economizer Discharge Pressure Sensor - xy Economizer Disch Press Sensor- xy Cprsr Normal Latch Bad sensor or LLID Remote Econ Disch Press Sensor xy Economizer Discharge Temperature Sensor - xy...
  • Page 26: Wiring

    Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors.
  • Page 27 Notes RTAF-SVX002D-EN...
  • Page 28 For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

Table of Contents