Trane R Series Installation, Operation And Maintenance Manual page 101

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Installation - Electrical
Table 50.
Multistate Input (continued)
BCI-C Object
Identifier
Object Name
Multi-State Input, 5
Model Information
Multi-State Input, 6
Cooling Type
Manufacturing
Multi-State Input, 7
Location
Table 51.
Binary Output
Object
Identifier
Object Name
Binary Output, 1
Chiller Auto Stop Command
Binary Output, 2
Remote Diagnostic Reset Command
Binary Output, 4
Noise Reduction Request
Table 52.
Binary Input
Object
Identifier
Object Name
Binary Input, 1
Run Enabled
Binary Input, 2
Local Setpoint Control
Binary Input, 3
Capacity Limited
Binary Input, 4
Chiller Running State
RTAC-SVX01J-EN
Description
Indicates the model type of the chiller.
Cooling type of the condenser.
Location where chiller was manufactured.
Description
Allows the chiller to run if conditions for
running are met.
Resets remotely diagnostics that can
be reset.
Requests chiller to enter mode to
reduce noise.
Description
Indicates if the chiller is available to run or is currently
running.
Indicates if the chiller is being controlled by local
setpoints instead of BAS setpoints.
Indicates if conditions may exist that prevent the
chiller from reaching setpoint.
Indicates if the chiller is running or stopped.
Object States
1 = RTA
2 = CVH
3 = CVG
4 = CVR
5 = CDH
6 = RTH
7 = CGW
8 = CGA
9 = CCA
10 = RTW
11 = RTX
12 = RTU
13 = CCU
14 = CXA
15 = CGC
16 = RAU
1 = Water Cooled
2 = Air Cooled
1 = Field Applied
2 = La Crosse
3 = Pueblo
4 = Charmes
5 = Rushville
6 = Macon
7 = Waco
8 = Lexington
9 = Forsyth
10 = Clarksville
11 = Ft. Smith
12 = Penang
13 = Colchester
14 = Curitiba
15 = Taicang
16 = Taiwan
17 = Epinal
18 = Golbey
Relinq
Default
Object States
Inactive = Stop
True
Active = Auto
Inactive = No Reset Request
False
Active = Reset Request
Inactive = Normal
False
Active = Reduced Noise
Object States
Inactive = Stop
Active = Auto
Inactive =Remote Control
Active = Local Control
Inactive = Not Limited
Active = Limited
Inactive = Off
Active = On
101