Trane R Series Installation, Operation And Maintenance Manual page 99

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Installation - Electrical
Table 48. Analog Input (continued)
Object
Identifier
Object Name
Analog Input, 25
Local Atmospheric Pressure
Analog Input, 26
Starts- Compressor 1A
Analog Input, 27
Starts- Compressor 1B
Analog Input, 28
Starts- Compressor 2A
Analog Input, 29
Starts- Compressor 2B
Analog Input, 34
Run Time- Compressor 1A
Analog Input, 35
Run Time- Compressor 1B
Analog Input, 36
Run Time- Compressor 2A
Analog Input, 37
Run Time- Compressor 2B
Analog Input, 42
Airflow Percentage- Circuit 1
Analog Input, 43
Airflow Percentage- Circuit 2
Analog Input, 44
Evaporator Entering Water Temp
Analog Input, 45
Evaporator Leaving Water Temp
Analog Input, 46
Condenser Entering Water Temp
Analog Input, 47
Condenser Leaving Water Temp
Analog Input, 48
High Side Oil Pressure- Compressor 1A
Analog Input, 49
High Side Oil Pressure- Compressor 1B
Analog Input, 50
High Side Oil Pressure- Compressor 2A
Analog Input, 51
High Side Oil Pressure- Compressor 2B
Analog Input, 56
Refrigerant Disch Temp- Ckt 1
Analog Input, 57
Outdoor Air Temperature
Analog Input, 58
Condenser Control Output
Analog Input, 59
Phase AB Voltage- Compressor 1A
Analo5 Input, 62
Phase AB Voltage- Compressor 1B
Analog Input, 65
Phase AB Voltage- Compressor 2A
Analog Input, 68
Phase AB Voltage- Compressor 2B
Analog Input, 71
Line 1 Current (in Amps)- Compressor 1A
Analog Input, 72
Line 2 Current (in Amps)- Compressor 1A
Analog Input, 73
Line 3 Current (in Amps)- Compressor 1A
Analog Input, 74
Line 1 Current (in Amps)- Compressor 1B
Analog Input, 75
Line 2 Current (in Amps)- Compressor 1B
Analog Input, 76
Line 3 Current (in Amps)- Compressor 1B
Analog Input, 77
Line 1 Current (in Amps)- Compressor 2A
Analog Input, 78
Line 2 Current (in Amps)- Compressor 2A
Analog Input, 79
Line 3 Current (in Amps)- Compressor 2A
Analog Input, 80
Line 1 Current (in Amps)- Compressor 2B
Analog Input, 81
Line 2 Current (in Amps)- Compressor 2B
Analog Input, 82
Line 3 Current (in Amps)- Compressor 2B
Analog Input, 83
Line 1 Current (%RLA)- Compressor 1A
Analog Input, 84
Line 2 Current (%RLA)- Compressor 1A
Analog Input, 85
Line 3 Current (%RLA)- Compressor 1A
Analog Input, 86
Line 1 Current (%RLA)- Compressor 1B
Analog Input, 87
Line 2 Current (%RLA)- Compressor 1B
Analog Input, 88
Line 3 Current (%RLA)- Compressor 1B
RTAC-SVX01J-EN
Description
Local atmospheric pressure.
Number of starts for compressor 1A.
Number of starts for compressor 1B.
Number of starts for compressor 2A.
Number of starts for compressor 2B.
Total run time of compressor 1A.
Total run time of compressor 1B.
Total run time of compressor 2A.
Total run time of compressor 2B.
Approximate airflow percentage of circuit 1.
Approximate airflow percentage of circuit 2.
Temperature of the water entering the evaporator. Degrees-Fahrenheit (64)
Temperature of the water leaving the evaporator. Degrees-Fahrenheit (64)
Temperature of the water entering the condenser. Degrees-Fahrenheit (64)
Temperature of the water leaving the condenser. Degrees-Fahrenheit (64)
Pressure of the oil at the high side of compressor
1A.
Pressure of oil at high side of compressor 1B.
Pressure of oil at high side of compressor 2A.
Pressure of oil at high side of compressor 2B.
Temperature of refrigerant being discharged from
Ckt 1.
Outdoor air temperature.
Percentage of condenser water flow being
requested by the chiller.
Phase AB voltage, compressor 1A.
Phase AB voltage, compressor 1B.
Phase AB voltage, compressor 2A.
Phase AB voltage, compressor 2B.
Line 1 Current (in Amps)- Compressor 1A
Line 2 Current (in Amps)- Compressor 1A
Line 3 Current (in Amps)- Compressor 1A
Line 1 Current (in Amps)- Compressor 1B
Line 2 Current (in Amps)- Compressor 1B
Line 3 Current (in Amps)- Compressor 1B
Line 1 Current (in Amps)- Compressor 2A
Line 2 Current (in Amps)- Compressor 2A
Line 3 Current (in Amps)- Compressor 2A
Line 1 Current (in Amps)- Compressor 2B
Line 2 Current (in Amps)- Compressor 2B
Line 3 Current (in Amps)- Compressor 2B
Line 1 Current (%RLA)- Compressor 1A
Line 2 Current (%RLA)- Compressor 1A
Line 3 Current (%RLA)- Compressor 1A
Line 1 Current (%RLA)- Compressor 1B
Line 2 Current (%RLA)- Compressor 1B
Line 3 Current (%RLA)- Compressor 1B
Units
PSI
None
None
None
None
Hours
Hours
Hours
Hours
Percent (98)
Percent (98)
PSI
PSI
PSI
PSI
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Percent (98)
Volts
Volts
Volts
Volts
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Percent (98)
Percent (98
Percent (98)
Percent (98)
Percent (98)
Percent (98)
99