Diagnostic Screen; Power-Up; Display Formats; Units - Trane R Series Installation, Operation And Maintenance Manual

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Controls Interface
Table 61
Setpoint options/conditions displayed (continued)
Option
Ckt Lockout
Ext. Chilled Water Setpt
Ext. Current Limit Setpt
Notes:
1 Pumpdown procedure are discussed in Maintenance section 10.
2 Used for liquid level control or to recover from pumpdown

Diagnostic Screen

The diagnostic screen (shown following) is accessible by
either pressing the blinking ALARMS key or by pressing
the Diagnostic tab on the screen tab selection.
A hex code and a verbal description appears on the display
as shown typically above.This is the last active diagnostic.
Pressing the "Reset All Active Diagnostics" will reset all
active diagnostics regardless of type, machine or
refrigerant circuit. Compressor diagnostics, which hold off
only one compressor, are treated as circuit diagnostics,
consistent with the circuit to which they belong. One
circuit not operating will not shut the chiller down.Viewing
the "Compressor" screen will indicate whether a circuit is
not operating and for what reason.
A complete listing of diagnostics and codes is included in
the Diagnostic Section.

Power-Up

On Power-Up, DynaView will cycle through three screens:
First Screen, Version # of the Boot, full version #
displayed.
• This screen will display for 5 seconds before
moving to second screen. Contrast is adjustable
from this screen.
Second Screen, Application or No Application.
• This screen will display for 5 seconds "A Valid
Application Is Present" or "A Valid Application Is
Not Present" .
Third Screen, First screen of the Application, the Chiller
Tab
RTAC-SVX01J-EN
Condition(s)
Explanation
State is displayed when EXV is open. Unit will not start with EXV manually set open,
Open
but will initiate valve closure first.
Locked Out
Circuit is locked out at Front Panel; other circuit may be available to run
Not Locked Out
Circuit is not locked out and is available to run
Allows unit to control setpoint; otherwise another loop controller in line will control, as
Enable/Disable
optionally wired.
Allows unit to control setpoint; otherwise another loop controller in line will control, as
Enable/Disable
optionally wired.

Display Formats

Units

Temperature settings are in °F or °C, depending on Display
Units settings. Settings can be entered in tenths or whole
degrees depending on a menu setting at theTechView.
Dashes ("-----") appearing in a temperature or pressure
report, indicates that the value is invalid or not applicable.

Languages

English plus two alternate languages may be installed
with DynaView and will reside in the main processor.
English will always be available. Alternate languages must
be installed usingTechView, Software Download View.

TechView

TechView™ is the PC (laptop) based tool used for servicing
Tracer CH530.Technicians that make any chiller control
modification or service any diagnostic withTracer CH530
must use a laptop running the software application
"TechView. " TechView is aTrane application developed to
minimize chiller downtime and aid the technicians
understanding of chiller operation and service
requirements.
117