Trane R Series Installation, Operation And Maintenance Manual page 156

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
Diagnostic Name
Target Severity
High Differential
Refrigerant Pressure
Circuit
- Circuit 2
High Evaporator
Liquid Level - Circuit
Circuit
1
High Evaporator
Liquid Level - Circuit
Circuit
2
High Evaporator
Chiller Immediate NonLatch
Refrigerant Pressure
High Evaporator
Chiller
Water Temperature
High Evaporator
Chiller
Water Temperature
High Oil
Temperature -
Cprsr 1B Immediate
Compressor 1B
High Oil
Temperature -
Cprsr 2B Immediate
Compressor 2B
156
Active Modes
Persist-
[Inactive
ence
Modes]
Normal
Latch
Cprsr Energized
Starter Contactor
Normal
Latch
Energized
[all Stop modes]
Starter Contactor
Normal
Latch
Energized
[all Stop modes]
Only effective if
either
Info and
1)Evap Wtr Flow
Special
Overdue,
Action (Pre
2)Evap Wtr Flow
NonLatch
RTAC
Loss, or
Refresh
3)Low Evap Rfgt
Rev 39)
Temp,-Unit Off,
diagnostic is
active.
Only effective if
either
Immediate
1)Evap Wtr Flow
Shutdown
Overdue
(Beginning
2)Evap Wtr Flow
Latch
with RTAC
Loss, or
Refresh
3)Low Evap Rfgt
Rev 39 )
Temp,-Unit Off,
diagnostic is
active.
Latch
Latch
The system differential pressure for the respective circuit was
above 275 Psid for 2 consecutive samples or more than 10
seconds
The liquid level sensor is seen to be at or near its high end of
range for 80 contiguous minutes while the compressor is
running. (The diagnostic timer will hold, but not clear when the
circuit is off). Design: 80% or more of bit count corresponding
to +21.2 mm or more liquid level for 80 minutes)
The liquid level sensor is seen to be at or near its high end of
range for 80 contiguous minutes while the compressor is
running. (The diagnostic timer will hold, but not clear when the
circuit is off). Design: 80% or more of bit count corresponding
to +21.2 mm or more liquid level for 80 minutes)
The evaporator refrigerant pressure of either circuit has risen
above 190 psig. The evaporator water pump relay will be de-
energized to stop the pump regardless of why the pump is
running (and the chiller will be prevented from starting) The
diagnostic will auto reset and the pump will return to normal
All
control when all of the evaporator pressures fall below 185 psig.
The primary purpose is to stop the evaporator water pump and
its associated pump heat from causing refrigerant side
pressures, close to the evaporator relief valve setting, when the
chiller is not running, such as could occur with Evap Water Flow
Overdue or Evaporator Water Flow Loss Diagnostics.
The leaving water temperature exceeded the high evap water
temp limit (TV service menu settable -default 105F) for 15
continuous seconds. The evaporator water pump relay will be
de-energized to stop the pump but only if it is running due to one
of the diagnostics listed on the left . The diagnostic will auto reset
and the pump will return to normal control when the
temperature falls 5 F below the trip setting. The primary purpose
is to stop the evaporator water pump and its associated pump
heat from causing excessive waterside temperatures and
waterside pressures when the chiller is not running but the evap
pump is on due to either Evap Water Flow Overdue, Evaporator
Water Flow Loss , or Low Evap Temp - Unit Off Diagnostics. This
diagnostic will not auto clear solely due to the clearing of the
enabling diagnostic.
The leaving water temperature exceeded the high evap water
temp limit (TV service menu settable -default 105F) for 15
continuous seconds, with one of the three diagnostics on the left
already active. The evaporator water pump relay will be de-
energized to stop the pump. The diagnostic can only be cleared
by a manual reset and will clear regardless of the temperature.
(although the diagnostic may reoccur based on the trip criteria).
The primary purpose is to stop the evaporator water pump and
its associated pump heat from causing excessive waterside
temperatures (and waterside pressures) when the chiller is not
running but the evap pump is on due to a pump override to "on"
(as can be caused by a bad flow switches failure to close and
prove flow).
The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
All
Limit Mode (aka Minimum Limit), the running compressor's
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.
The respective oil temperature as supplied to the compressor,
exceeded 200 F for 2 consecutive samples or for over 10
seconds. Note: As part of the Compressor High Temperature
All
Limit Mode (aka Minimum Limit), the running compressor's
female load step will be forced loaded when its oil temperature
exceeds 190F and returned to normal control when the oil
temperature falls below 170 F.
Criteria
RTAC-SVX01J-EN
Reset
Level
Remote
Remote
.
Remote
Remote
Remote
Local
Remote
Remote

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents