Trane R Series Installation, Operation And Maintenance Manual page 122

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Controls Interface
Table 63. Configuration View Items (continued)
Tab
Item
Remote Interface
Control Input Accessories/Options
Control Output Accessories/Options
Short Circuit Rating
Control Panel Accessories
Refrigerant Service Valves
Compressor Sound Attenuator Option
Appearance Options
Features Installation Accessories
Factory Test
Control, Label, and Literature
Language
Special Order
Custom Comm 3 ICS address
Status Relay #1 J2-10,11,12
Status Relay #2 J2-7,8,9
Status Relay #3 J2-4,5,6
Status Relay #4 J2-1,2,3
Phase Unbalance Trip
Phase Unbalance Grace Period
Maximum Acceleration Time
Starter Feature
External Chilled Water Setpoint
Detection
External Current Limit Water
Setpoint Detection
Custom Unit Voltage
• The Model Number field contains the model number stored in the DynaView.
• The Confirm Code field contains the confirm code stored in the DynaView. The confirm code is a four-digit hex value that is a mathematical
Name-
calculation of the model number. This number has one to one correlation to a specific model number and is used to verify that the model
number was entered properly.
plate
• The Serial Number field contains the serial number stored in the DynaView.
• This model number and confirmation code must be know when the main processor requires replacement.
122
Default
Description
N - No remote interface
C - Tracer Comm 3 interface
B - BACnet communication interface
L -Lon Talk Communication interface (LCI)
N -No remote input
R -Remote leaving water temp setpoint
C -Remote current limit setpoint
B -Remote leaving temp setpoint and remote current limit setpoint
N -No output options
A -Alarm relay
C -Icemaking
D -Icemaking and alarm relay
0 - No short circuit withstand rating
5 -Default short circuit rating
6 - High amp short circuit rating
N - No convenience outlet
A - 15A 115V convenience outlet (60HZ)
0 - No suction services valves
1 - Suction service valves
0 - No sound attenuator
1 - Factory installed sound attenuator
N - No appearance options
A - Architectural louvered panels
C - Half Louvers
P - Painted unit
L - Painted unit with full louvered panels
H - Painted unit with half louvered panels
K - Painted unit with access guards
W - Painted w/access guards and half louvers
N - No installation accessories
R - Neoprene Isolators
F - Flanged water connection kit
G - Neoprene isolators and flange wtr conn kit
0 - No factory run test
E - English
G - Chinese
X - Standard catalog configuration
S - Unit has special order feature
55
1-64 REM = C
Alarm - Latching
None, Alarm - Latching (Active diagnostic persistence latching), Alarm - Auto reset
(Active diagnostic persistence non-latching), Alarm (Active diagnostic persistence
Chiller Running
latching or non-latching), Alarm Ckt1 (Active diagnostic persistence latching or non-
Maximum Capacity
latching), Alarm Ckt2 (Active diagnostic persistence latching or non-latching),
Chiller Limit Mode (With 20 minute filter), Circuit 1 Running, Circuit 2 Running, Max
Chiller Limit Mode
Capacity
COOP = A, D or X
30
10-50%
90
30-255 Sec
3
1-255 Sec
All Enabled
Contactor Integrity Test, Phase Reversal Detect, Phase Unbalance Detect
2-10 VD
2-10 VDC, 4-20 mA CIOP = C or B
2-10 VDC
2-10 VDC, 4-20 mA CIOP = C or B
400
380,400,415 VOLT = D
RTAC-SVX01J-EN