Trane R Series Installation, Operation And Maintenance Manual page 158

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Diagnostics
Table 67. Main processor diagnostics (continued)
Affects
Diagnostic Name
Target Severity
Low Evaporator
Liquid Level - Circuit
None
1
Low Evaporator
Liquid Level - Circuit
None
2
Low Evaporator
Refrigerant
Circuit Immediate
Temperature -
Circuit 1
Low Evaporator
Refrigerant
Circuit Immediate
Temperature -
Circuit 2
Low Evaporator
Evap
Temp - Ckt 1: Unit
Pump
Off
Low Evaporator
Evap
Temp - Ckt 2: Unit
Pump
Off
Low Oil Flow -
Cprsr
Compressor 1A
Low Oil Flow -
Cprsr
Compressor 1B
158
Active Modes
Persist-
[Inactive
ence
Modes]
Starter Contactor
Info
NonLatch
Energized
[all Stop modes]
Starter Contactor
Info
NonLatch
Energized
[all Stop modes]
All Ckt Running
Latch
Modes
All Ckt Running
Latch
Modes
Unit in Stop Mode,
or in Auto Mode
Special
NonLatch
and No Ckt's
Mode
Energzd
[Any Ckt Energzd]
Unit in Stop Mode,
or in Auto Mode
Special
NonLatch
and No Ckt's
Mode
Energzd
[Any Ckt Energzd]
Cprsr Energized
Immediate
Latch
and Delta P above
35 Psid
Cprsr Energized
Immediate
Latch
and Delta P above
35 Psid
Criteria
The liquid level sensor is seen to be at or near its low end of range
for 80 contiguous minutes while the compressor is running.
Design: 20% or less of bit count corresponding to -21.2 mm or
less liquid level for 80 minutes)
The liquid level sensor is seen to be at or near its low end of range
for 80 contiguous minutes while the compressor is running.
Design: 20% or less of bit count corresponding to -21.2 mm or
less liquid level for 80 minutes)
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the
Low Refrigerant Temperature Cutout Setpoint for 1125 F-sec
with a 8 F-sec/sec max integral rate applied during circuit
startup transient (or 4ºF-s/s if manifolded and only one cprsr
running) while the circuit was running early in the circuit's cycle.
The minimum LRTC setpoint is -5 F (18.7 Psia) the point at which
oil separates from the refrigerant. During the time that the trip
integral is non zero, the unload solenoid(s) of the running
compressors on the circuit, shall be energized continuously and
the load solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps above the
cutout setpoint. The integral is held nonvolatily though power
down, is continuously calculated, and can decay during the
circuit's off cycle as conditions warrant.
The inferred Saturated Evap Refrigerant Temperature
(calculated from suction pressure transducer dropped below the
Low Refrigerant Temperature Cutout Setpoint for 1125 F-sec
with a 8 F-sec/sec max integral rate applied during circuit
startup transient (or 4ºF-s/s if manifolded and only one cprsr
running) while the circuit was running early in the circuit's cycle.
The minimum LRTC setpoint is -5 F (18.7 Psia) the point at which
oil separates from the refrigerant. During the time that the trip
integral is non zero, the unload solenoid(s) of the running
compressors on the circuit, shall be energized continuously and
the load solenoid shall be off. Normal load/unload operation will
be resumed if the trip integral decays to zero by temps above the
cutout setpoint. The integral is held nonvolatily though power
down, is continuously calculated, and can decay during the
circuit's off cycle as conditions warrant.
Any of the evap sat temps fell below the water temp cutout
setting while the respective evap liquid level was greater than -
21.2mm for 150 degree F seconds while Chiller is in the Stop
mode, or in Auto mode with no compressors running. Energize
Evap Water pump Relay until diagnostic auto resets, then return
to normal evap pump control. Automatic reset occurs when
either the evap temp rises 2 F (1.1 C) above the cutout setting
or the liquid level falls below -21.2mm for 30 minutes
Any of the evap sat temps fell below the water temp cutout
setting while the respective evap liquid level was greater than -
21.2mm for 150 degree F seconds while Chiller is in the Stop
mode, or in Auto mode with no compressors running. Energize
Evap Water pump Relay until diagnostic auto resets, then return
to normal evap pump control. Automatic reset occurs when
either the evap temp rises 2 F (1.1 C) above the cutout setting
or the liquid level falls below -21.2mm for 30 minutes
The intermediate oil pressure transducer for this compressor
was out of the acceptable pressure range for 15 seconds, while
the Delta Pressure was greater than 35 Psid.: Acceptable range
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,
The intermediate oil pressure transducer for this compressor
was out of the acceptable pressure range for 15 seconds, while
the Delta Pressure was greater than 35 Psid.: Acceptable range
is 0.50 > (PC-PI) / (PC-PE) for the first 2.5 minutes of operation,
and 0.25 > (PC-PI) / (PC-PE) thereafter,
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Local
Local
RTAC-SVX01J-EN