The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
Minimum Clearance from Top of Front Facing:
Mantel
min. 16-1/2"
(419mm)
Ceiling
52"
(813mm) from top of front facing
Side Wall to Unit:
15"*
(381mm)
Horizontal Vent Clearances to Combustibles:
Top
3"
(76mm)
Side
2"
(51mm)
Bottom
2"
(51 mm)
Vertical Vent Clearances to Combustibles:
All Sides
2"
(51mm)
Alcove Clearances:
Min. Depth
36"
(914mm)
Min. Width*
84"
(2134mm)
Min. Height
84"
(2032mm)
* Alcove side wall must have a minimum of 15" (381mm) clearance on one side.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fi replace and vent system be installed only in
accordance with these instructions.
Regency
®
L676E Direct Vent Gas Fireplace

CLEARANCES

INSTALLATION