Cabinet Requirements For J-Ex4200 Switches - Dell PowerConnect J-EX4200 Hardware Manual

Powerconnect j-series ethernet switch
Hide thumbs Also See for PowerConnect J-EX4200:
Table of Contents

Advertisement

Dell PowerConnect J-Series J-EX4200 Ethernet Switch Hardware Guide
Table 26: Rack Requirements and Specifications for the Switch (continued)
Rack Requirement
Guidelines
Rack size and strength
Rack connection to
building structure
Related
Documentation

Cabinet Requirements for J-EX4200 Switches

64
Ensure that the rack complies with one of these standards:
A 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number
EIA-310–D) published by the Electronics Industry Association (
Ensure that the rack rails are spaced widely enough to accommodate the switch chassis' external
dimensions . The outer edges of the front-mounting brackets extend the width of the chassis to
19 in. (48.2 cm).
The rack must be strong enough to support the weight of the switch. A fully configured J-EX4200
switch weighs up to 22 lb (10 kg). If you mount multiple units in one rack, that rack must support
the total weight of the units.
Ensure that the spacing of rails and adjacent racks allows for the proper clearance around the
switch and rack as specified in "Clearance Requirements for Airflow and Hardware Maintenance
for J-EX4200 Switches" on page 66.
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.
One pair of mounting brackets for mounting the switch on two posts of a rack is supplied
with each switch. For mounting the switch on four posts of a rack or cabinet, you can
order a four-post rack-mount kit separately.
Chassis Physical Specifications for J-EX4200 Switches on page 5
Rack-Mounting and Cabinet-Mounting Warnings for J-EX Series Switches on page 185
Clearance Requirements for Airflow and Hardware Maintenance for J-EX4200 Switches
on page 66
Mounting a J-EX4200 Switch on Two Posts in a Rack or Cabinet on page 92
Mounting a J-EX4200 Switch on Four Posts in a Rack or Cabinet on page 96
Mounting a J-EX4200 Switch in a Recessed Position in a Rack or Cabinet on page 100
You can mount the switch in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
Cabinet size
Clearance requirements
Cabinet airflow requirements
Table 27 on page 65 provides the cabinet requirements and specifications for the switch.
http://www.eia.org
).