Installation of EDS files

Step 1
Step 2
3-2

Configuring the Option Board

Step 3
Step 4
Step 5

Configuring Drive Parameters and Option Board

For each of the MX2 Inverter models, a specific EDS file exists for the Option
Board. The EDS files contain specific parameter data (default, ranges)
depending on the model. Perform the following steps to install the EDS files
prior to configure the network.
Download the EDS files named 3G3AX-MX2-DRT-@-E.eds for the
3G3AX-MX2-DRT-E
industrial.omron.eu).
Install / add these EDS files to the DeviceNet Master Unit configuration pro-
gram used to configure your DeviceNet master.
All Option Board parameters are stored in the MX2-A@ Inverter. This allows
for easy replacement of the Option Board without the need to re-configure.
After connecting the Option Board to an MX2-A@ Inverter for the first time
however, proceed with the following steps:
Set the DeviceNet node number / MAC ID by configuring inverter parameter
P192. Use either the Inverter keypad or any other method of configuring the
inverter parameters. See note 1.
Table 7 Configuration of Node Number
Param
P192
DeviceNet Node
Address
When using the automatic / fixed allocation mechanism of the DeviceNet Mas-
ter Unit (see next section), choose the required Output and Input assembly
pair using inverter parameter P046 Default Connection Path.
Table 8 Default Connection Path
P046
value
0
Basic Speed IO
1
Extended Speed IO (default)
2
Extended Speed and Torque Control
3
Special IO
4
Extended Control IO
5
Extended Control IO and Multi Function IO Monitor
6
Flexible Format
7
Extended Speed and Acceleration Control
It is recommended to set C102 = 3 to prevent the Inverter reset input and
Stop/reset button from interfering with Option Board during operation. Setting
C102 to another value causes the Option Board to reset when a trip condition
is cleared. See the MX2 User's manual (Cat. No. I570) for details on this
parameter.
Table 9 Configuration of Inverter Reset Mode Selection
Param
C102
Reset mode selection Set to 3 "Resetting only trip" (recommended setting)
Option
Board
Description
0 to 63 (default: 63)
Description
Description
SECTION 3
via
the
Omron
website
Setting
Assembly nr (Hex)
Output
20
21
123
100
101
101
139
110
Setting
(http://
Input
70
71
173
150
151
153
159
111
15