Omron MX2 DEVICENET OPTION BOARD User Manual page 30

Mx2 devicenet option board
Table of Contents

Advertisement

Configuring the Option Board
Step 6
Step 7
Step 8
16
Inverter registers P044, P045 and P048 configure the DeviceNet network-
related parameters. Adjust these to configure required action in case a field-
bus network IDLE mode behaviour and/or a fieldbus failure occurs.
Table 10 Configuration of DeviceNet Parameters
Param
Description
P044
Network Error Timer
P045
Action on Network
Error
P048
Action on Network
Idle Mode
Registers A001 and A002 are used by the Inverter to adjust the frequency
source and control source. If the second motor parameter set is used, regis-
ters A201 and A202 also have to be set. Adjust these in accordance with the
following table:
Table 11 Configuration of Source Selection Parameters
Param
Description
A001
Motor 1
Frequency Source
A002
Motor 1 Run
Command Source
Registers P033, P036, C021, C022 and C026 are used by the Inverter to
adjust some Inverter function sources. If required, adjust these in accordance
with the following table:
Table 12 Configuration of Other Selection Parameter
Param
Description
P033
Torque Command
Source
P036
Torque Bias Mode
C021
Output Terminal 11
Source
C022
Output Terminal 12
Source
C026
Alarm Relay Source
Setting
Communication watchdog timer while running.
Note additional to DeviceNet inactivity / watchdog
timer.
0 to 9999 in 0.1 s unit. Set to 0 to disable.
Set to 0 for inverter trip (Default)
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
Set to 0 for inverter trip (Default)
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
Setting
For option board as source:
Set to 4 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Modbus network input" in case of Flexible
format (P046 is 6)
Setting
For option board as source:
Set to 6 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Digital Operator input" for Flexible format
(P046 is 6)
For option board as source:
Set to 5 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Digital Operator input" for Flexible format
(P046 is 6)
Set to 63 for option board as source
Set to 63 for option board as source
Set to 63 for option board as source (optional)
Section 3-2