Configuring the Network
Note 1
Note 2
Note 3
20
For a particular connection type (Poll, COS, Cyclic), only one of the pre-
defined pairs as listed for the Default Connection Path (P046) can be config-
ured. Please note in case a non-matching pair is selected, no error is gener-
ated. For either the input or output assembly, the matching pair will be
configured.
Third party masters may require to set the inverter parameter P046 Default
Connection Path corresponding to the User-set selection.
When using only COS or Cyclic connection, be sure to put the Network Error
Timer P044 in the Inverter higher than the COS/Cyclic Heart beat timer.
Tip
In case of any errors during configuring the network, please refer to SECTION
5 Troubleshooting and Maintenance.
For the user-set allocation, the DeviceNet configurator is used. The output
and input data assemblies of the slaves can be allocated freely to the Master
Units IO blocks. Also specific connection variants (Poll, Bit-Strobe, COS,
Cyclic) can be selected based on the settings in the EDS file.