Omron MX2 DEVICENET OPTION BOARD User Manual page 31

Mx2 devicenet option board
Table of Contents

Advertisement

Configuring the Option Board
Step 9
Step 10
Note 1
The Flexible format (assembly 139/159) gives you the freedom to select any
Inverter Modbus register for Cyclic Data Exchange. Inverter registers P160 –
P179 are used to configure and map the exchanged Modbus registers. Please
refer to APPENDIX F Flexible Format on page 79 for more detail.
Table 13 Configuration of Flexible Mapping
Param
Description
P160
Output Register 1
contents
P161
Output Register 2
contents
P162
Output Register 3
contents
P163
Output Register 4
contents
P164
Output Register 5
contents
P165
Output Register 6
contents
P166
Output Register 7
contents
P167
Output Register 8
contents
P168
Output Register 9
contents
P169
Output Register 10
contents
P170
Input Register 1 con-
tents
P171
Input Register 2 con-
tents
P172
Input Register 3 con-
tents
P173
Input Register 4 con-
tents
P174
Input Register 5 con-
tents
P175
Input Register 6 con-
tents
P176
Input Register 7 con-
tents
P177
Input Register 8 con-
tents
P178
Input Register 9 con-
tents
P179
Input Register 10
contents
Restart the MX2-A@ Inverter for the changes to take effect. See note 1 and 2.
Alternative ways for configuring inverter parameters and resetting the inverter
are use the OMRON CX-Drive tool, use CX-Integrator with the unit's EDS file
(see SECTION 4 Operations and Monitoring on page 21), or use Explicit mes-
sages to access the parameters directly (refer to APPENDIX E DeviceNet
Explicit Messages on page 71).
Setting
Modbus register mapped into flexible output
word 1
Modbus register mapped into flexible output
word 2
Modbus register mapped into flexible output
word 3
Modbus register mapped into flexible output
word 4
Modbus register mapped into flexible output
word 5
Modbus register mapped into flexible output
word 6
Modbus register mapped into flexible output
word 7
Modbus register mapped into flexible output
word 8
Modbus register mapped into flexible output
word 9
Modbus register mapped into flexible output
word 10
Modbus register mapped into flexible input word 1
Modbus register mapped into flexible input word 2
Modbus register mapped into flexible input word 3
Modbus register mapped into flexible input word 4
Modbus register mapped into flexible input word 5
Modbus register mapped into flexible input word 6
Modbus register mapped into flexible input word 7
Modbus register mapped into flexible input word 8
Modbus register mapped into flexible input word 9
Modbus register mapped into flexible input
word 10
Section 3-2
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3g3ax-mx2-drt-e

Table of Contents