Omron CQM1H-SCB41 Operation Manual page 309

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

K3T@ Intelligent Signal Processor Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Set Value H with Bank (Continuous Units)
(Sequence No. 309)
This sequence writes set value H of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value L with Bank (Continuous Units)
(Sequence No. 310)
This sequence writes set value L of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value LL with Bank (Continuous Units)
(Sequence No. 311)
This sequence writes set value LL of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O5 with Bank (Continuous Units)
(Sequence No. 312)
This sequence writes set value O5 of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O4 with Bank (Continuous Units)
(Sequence No. 313)
This sequence writes set value O4 of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O3 with Bank (Continuous Units)
(Sequence No. 314)
This sequence writes set value O3 of a bank not in use for continuous units. The word allocation is identical to
that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
294
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units
(2 digits BCD)
+2
Bank No.
(2 digits BCD)
+3 to +4 Set value
(5 digits BCD)
+96 to
Set value
+97
(5 digits BCD)
Appendix I
Data
0004 to 0098
01 to 32
01 to 04
00000 to 99999
Negative sign: F (5th digit BCD)
Example 12345
Example 1234
+2
2345
+2
+3
0001
+3
Same as above
1234
000F

Advertisement

Table of Contents
loading

Table of Contents