E5@K Digital Controller Write Protocol
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write LBA Detection Time (Sequence No. 059)
Writes the LBA detection time.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write MV at Stop Time and at PV Error (Sequence No. 060)
Writes the MV at stop time and the MV at PV error.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write MV Limits (Sequence No. 061)
Writes the MV upper limit, MV lower limit, and MV change rate limit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
+0
Number of send data words
+1
(Undefined)
LBA detection time
+2
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
LBA detection time (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
MV at stop time
+3
MV at PV error
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
MV at stop time (4 digits BCD)
+3
MV at PV error (4 digits BCD)
+0
Number of send data words
(Undefined)
+1
+2
MV upper limit
+3
MV lower limit
+4
MV change rate limit
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits BCD)
+2
MV upper limit (4 digits BCD)
+3
MV lower limit (4 digits BCD)
+4
MV change rate limit
(4 digits BCD)
Unit No.
0003 (fixed)
00 to 31
0000 to 9999
Unit No.
0004 (fixed)
00 to 31
0000 to 1050
0000 to 1050
Unit No.
0005 (fixed)
00 to 31
MV lower limit +1 to 1050
Heating/cooling control time: 0000 to 1050
0000 to MV upper limit –1
0000 to 1000
Appendix D