Omron CJ - 10-2005 Manual page 91

Programming consoles
Table of Contents

Advertisement

Inputting Instructions
Designating Indirect DM/EM Addresses
Indirect DM Addresses
Mode
BCD
CH
*DM
Binary
CH
*DM
Indirect EM Addresses
Mode
BCD
With bank
SHIFT
BCD
Current bank
SHIFT
Binary
With bank
SHIFT
Binary
Current bank
SHIFT
• In BCD mode, indirect DM/EM addresses can be specified from D00000
to D09999 and E00000 to E09999. Use binary mode to specify D10000 to
D32767 and E10000 to E32767.
• If 8000 to FFFF Hex are specified as indirect DM addresses in binary
mode, E00000 to E32767 in bank 0 of the EM Area will be designated.
• If 8000 to FFFF Hex are specified as indirect EM addresses in binary
mode, E00000 to E32767 in the bank following the one specified will be
designated.
Key sequence
*D00010
Number
@D00010
CH
Number
*DM
Key sequence
*E0_00010
*EM_
Number
EM_/EXT
*E00010
*EM
Number
WR/LR
@E0_00010
*EM_
*EM_
SHIFT
Number
EM_/EXT
EM_/EXT
@E00010
*EM
*EM
Number
SHIFT
WR/LR
WR/LR
Section 4-1
Display example
000202 MOV
SV A
*D00010
000202 MOV
SV A
@D00010
Display example
000202 MOV
SV A
*E0_00010
000202 MOV
SV A
*E00010
000202 MOV
SV A
@E0_00010
000202 MOV
SV A
@E00010
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents