2. M-NET control
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
*1 Connected with simple remote controller.
*2 To wire PAR-30MAAC, use a wire with a diameter of 0.3 mm
*3 When a PAR-30MAAC is connected to a group, no other MA remote
controllers can be connected to the same group.
(L
)
Transmission cables
i
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25
[AWG16]
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
2
[AWG22]
SYSTEM DESIGN
ME Remote controller cables
Sheathed 2-core cable (unshielded)
CVV
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS :
PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable
C7-R Rev.
MA Remote controller cables
2
0.3 1.25
[AWG22 16]
2
(0.75 1.25
[AWG18 16])
Max length : 200m [656ft]