Control; 13-1.Transmission Cable Specifications - Mitsubishi Electric City Multi PWFY-P100VM-E-BU Data Book

Air conditioning systems
Hide thumbs Also See for City Multi PWFY-P100VM-E-BU:
Table of Contents

Advertisement

13. CONTROL

13-1. Transmission cable specifications
13. CONTROL
Transmission cables
PWFY-P100VM-E-BU
Transmission cables
Shielding wire (2-core)
Type of cable
CVVS, CPEVS or MVVS
Cable diameter
More than 1.25 mm
Remarks
PWFY-EP100VM-E1/E2-AU
Transmission cables
Shielding wire (2-core)
Type of cable
CVVS, CPEVS or MVVS
Cable diameter
More than 1.25 mm
Remarks
CVVS, MVVS: PVC insulated PVC sheathed shielded control cable
CVV, MVV: PVC insulated PVC sheathed control cable
CPEVS: PE insulated PVC sheathed shielded communication cable
MEES19K013
MA Remote controller cables
Sheathed 2-core cable (shielded)
CVVS
2
0.3 ~ 1.25 mm
-
Max.length: 200 m
MA Remote controller cables
Sheathed 2-core cable
CVV (unshielded)
2
0.3 ~ 1.25 mm
-
Max.length: 200 m
External input
Sheathed multi-core cable
(shielded)
CVVS or MVVS
2
0.3 ~ 0.5 mm
Max.length: 100 m
External input
Sheathed multi-core cable
CVV or MVV (unshielded)
2
0.3 ~ 0.5 mm
Max.length: 100 m
AIR TO WATER
External output
Sheathed multi-core cable
(unshielded)
CVV or MVV
2
0.3 ~ 1.25 mm
Rated voltage: L1-N: 220 ~ 240 V
Rated load: 0.6 A
External output
Sheathed multi-core cable
(unshielded)
CVV or MVV
2
0.3 ~ 1.25 mm
Rated voltage: L1-N: 220 ~ 240 V
Rated load: 0.6 A
2
2
43