Mitsubishi Electric CITY MULTI PEFY-P22VMS-E-S Data Book page 327

Table of Contents

Advertisement

2. M-NET control
2-4-3. System examples
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
PUHY
OC
TB7
51
CN40
CN41
DipSW2-1
ON
TB3
TB2
202
*3
SC
Power supply unit
(PAC-SC51KUA)
*2
000 or 201
SC*3
203
*3
SC
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
NOTE:
1. Address should be set to Indoor units, LOSSNAY and system controller.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
3. When a PAR-30MAAC is connected to a group, no other MA remote controllers can be connected to the same group.
PUHY
OC
TB7
91
CN40
CN41
DipSW2-1
ON
TB3
Group 1
Indoor unit
01
02
TB5
TB15
TB5
*1
SRU
MA R/C
*1
Wireless R/C
Group 31
Group 32
Indoor unit
41
42
TB5
TB15
TB5
SRU
*1
142
ME R/C
*1
Wireless R/C
SYSTEM DESIGN
PUHY
OC
TB7
98
CN40
CN41
DipSW2-1
ON
TB3
Group 2
03
TB15
TB5
TB15
TB2
Transmission Booster
PAC-SF46EPA
Group 33
Group 34
LOSSNAY
43
45
TB5
TB5
TB15
143
PZ-52SF-E
MA R/C
C7-R Rev.
Group 21
30
TB3
TB5
TB15
MA R/C
MA R/C
(Main)
(Sub)
Group 35
Group 36
LOSSNAY
46
47
TB5
TB5
TB15
147
MA R/C
MA R/C
PZ-52
(Main)
(Sub)
SF-E
4 - 50