4. Outdoor Installation
4-2. Spacing
External dimension (Fig.4-2-1a,b)
Fig. 4-2-1a PUMY-P-YHMC-C/VHMC-S dimension Fig. 4-2-1b PUMY-P-YKMC-C dimension
4-2-1. Spacing individual PUMY-P-YHMC-C/VHMC-S/YKMC-C
Follow Fig. 4-2-2 ~ 7 to space individual PUMY-P-YHMC-C/VHMC-S/YKMC-C at the installation site.
Fig. 4-2-2
Obstacles at rear only
Fig. 4-2-4
Obstacles at rear and sides only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 4-2-6
Obstacles at front and rear only
mm[in.]
mm[in.]
Fig. 4-2-3
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 4-2-5
Obstacles at front only
1500
[59-1/16"]
500
[19-11/16"]
* NO upward airflow outlet guide.
Fig. 4-2-7
Obstacles at rear, sides and above only
SYSTEM DESIGN
PUMY-P-YHMC-C/VHMC-S/YKMC-C can connect Indoor unit sized
P15 to P140 ; and can connect totally 1-12 Indoor units with total
capacity ranged 50%-130% of the outdoor unit capacity.
Connectable Indoor capacity
PUMY-P100YHMC-C/VHMC-S 5.6 - 14.6kW
PUMY-P125YHMC-C/VHMC-S 7.1 - 18.2kW
PUMY-P140YHMC-C/VHMC-S 8.0 - 20.2kW
PUMY-P200YΚMC-C
11.2 - 29.1kW
PUMY-P250YΚMC-C
12.5 - 32.5kW
4-2-2. Spacing grouped PUMY-P-YHMC-C/VHMC-S/YKMC-C
Follow Fig. 4-2-8 ~ 13 to space grouped PUMY-P-YHMC-C/VHMC-S/YKMC-C at the installation site.
Leave 10 mm [13/32"] space or more between PUMY-P-YHMC-C/VHMC-S/YKMC-C units.
* When using an optional air outlet guide,
the clearance is 1000 mm [39-3/8"] or more.
Fig. 4-2-8
Obstacles at rear or front only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 4-2-10
Obstacles at front and rear only
* Using an optional air outlet guide for upward
airflow, the clearance >= 1500 mm [59-1/16"].
Fig. 4-2-12
Parallel groups arrangement
C7-R Rev.
Connectable Indoor unit
P15-P125, 1-8 units
P15-P140, 1-10 units
P15-P140, 1-12 units
P15-P140, 1-12 units
P15-P140, 1-12 units
mm[in.]
* In case of side-by-side installation, <=3 units;
* Do not install the optional air outlet guides
for upward airflow.
Fig. 4-2-9
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 4-2-11
Parallel individuals arrangement
* Stacked layer <= 2 units;
* Side-by-side stacked groups <= 2 groups;
Fig. 4-2-13
Stacked groups arrangement
4 - 27