3. System remote controller
(1-2) Output
Non-voltage Relay contact or transistor is available for output. Only one can be used at a time.
(a) Non-voltage Relay Contact Outputs
• To use X1 and Y1 relay, obtain one that satisfies the following specifications.
Operating coil
[Applied load]
MAX: 24 VDC, 5 W (Built-in diode)
MIN: 5 VDC, 2 mW (Built-in diode)
*1 AC loads cannot be connected.
*2 Provide a power supply (V1, V2) that matches the load and relay to be used.
• To drive a direct load, use ones within the following.
[Applied load]
CAUTION
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
• Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.
• Do not connect the wires directly from the top of the control panel to the terminal block.
Moisture may enter this device along the wiring and cause electric shock or fire.
Power supply
V1 (DC)
Y1
Y1
X1
Ch1
Device
side
(OFF)
(OFF)
ON/OFF, (ON)
ON/OFF, (ON)
( ) is in the case of a pulse.
Tightening torque for terminal screws: 1 N·m
CONTROLLER
Operate (ON) output :
Contacts closed
Load
Stop (OFF) output :
Contacts open
Power supply
*Upon pulse output, the (ON), (OFF)
V2
V2 (DC)
Field
contacts close according to the output
Connections
content. ((ON) and (OFF) refer to the
junctions in the diagram.)
CN04
Ch2
C7-R Rev.
3 - 33