1. SPECIFICATIONS
Power source
Cooling capacity
(Nominal)
Power input
Current input
COP (kW / kW)
Indoor
Temp. range of
Outdoor
cooling
Heating capacity
(Nominal )
Power input
Current input
COP (kW / kW)
Temp. range of
Indoor
Outdoor
heating
Total capacity
Connectable
Model / Quantity
indoor unit
Sound pressure level
(measured in anechoic room)
Refrigerant piping
Liquid
diameter
Gas
External finish
External dimension H x W x D
Net weight
Heat exchanger
Compressor
Type x Quantity
Manufacturer
Starting method
Motor output
Case heater
Lubricant
FAN
Air flow rate
External static press.
Type x Quantity
Control, Driving mechanism
Motor output
HIC circuit
(HIC: Heat Inter-Changer)
Protection
High pressure protection
Inverter circuit (COMP. / FAN)
Compressor
Fan motor
Defrosting method
Refrigerant
Type x Original charge
Control
Drawing
External
Wiring
Refrigerant circle
Standard
Document
attachment
Accessory
Optional parts
Remark
Note :
*1 Nominal cooling conditions
Indoor :
27°CDB/19°CWB (81°FDB/66°FWB)
Outdoor :
35°CDB (95°FDB)
Pipe length :
7.5 m (24-9/16 ft)
Level difference :
0 m (0 ft)
*3 Liquid pipe diameter: 12.7mm in case of farthest piping length is longer than 60m
* Nominal conditions *1, *2 are subject to JIS B8615-1.
* Due to continuing improvement, above specifications may be subject to change without notice.
PUMY-P200YKMC-C
3-phase 4-wire 380V 50Hz
kW
*1
kcal / h
*1
*1
BTU / h
kW
A
W.B.
15 ~ 24°C (59 ~ 75°F)
D.B.
- 5 ~ 46°C (23 ~ 115°F)
10 to 46°CD.B. (50 to 115°FD.B.) : in case of connecting PKFY-P15-P25 type indoor unit.
kW
*2
kcal / h
*2
*2
BTU / h
kW
A
D.B.
15 ~ 27°C (59 ~ 81°F)
W.B.
-20 ~ 15°C (-4 ~ 59°F)
50 ~ 130% of outdoor unit capacity
P15 ~ P140 / 1 ~ 12
dB <A>
mm (in.)
ø9.52 (ø3/8) (*3)
mm (in.)
ø22,2 (ø7/8)
Galvanized steel sheet
<MUNSELL 3Y 7.8/1.1>
mm
1,338 x 1,050 x 330 (+30)
in.
52-11/16 x 41-3/8 x 13 (+1-3/16)
kg (lbs)
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp. x 1
MITSUBISHI ELECTRIC CORPORATION
kW
kW
m
3
/ min
L / s
cfm
Propeller fan x 2
DC-control, Direct-driven by motor
kW
HIC circuit
High pressure sensor, High pressure switch 4.15 MPa
Over-heat protection, Over-current protection
Compressor thermo protection, Over-current protection
Over-heat protection, Voltage protection
Auto-defrost mode (Reversed refrigerant circle)
R410A x 7.3kg (17 lbs)
LEV circuit
YKM-BK01-J769
YKM-BH79-B678
RC_VBN-11Q067
Installation Manual
Grounded lead wire x 2
Joint: CMY-Y62-G-E
Header:CMY-Y64/68-G-E
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
*2 Nominal heating conditions
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
OUTDOOR UNITS
22.4
19,300
76,400
8.39
13.7
2.67
10 to 46°CD.B. (50 to 115°FD.B.) : in case of connecting PKFY-P15-P25 type indoor unit.
25.0
21,500
85,300
6.24
10.2
4.01
56 / 58
140 (309)
Inverter
4.7
-
FV50S
140
2333
4943
0 Pa
0.15 x 2
High pressure sensor, High pressure switch 4.15 MPa
Compressor thermo protection, Over-current protection
PUMY-P250YKMC-C
3-phase 4-wire 380V 50Hz
25.0
21,500
85,300
10.34
16.9
2.42
15 ~ 24°C (59 ~ 75°F)
- 5 ~ 46°C (23 ~ 115°F)
27.3
23,500
93,100
7.26
11.9
3.76
15 ~ 27°C (59 ~ 81°F)
-20 ~ 15°C (-4 ~ 59°F)
50 ~ 130% of outdoor unit capacity
P15 ~ P140 / 1 ~ 12
58 / 61
ø9.52 (ø3/8) (*3)
ø22,2 (ø7/8)
Galvanized steel sheet
<MUNSELL 3Y 7.8/1.1>
1,338 x 1,050 x 330 (+30)
52-11/16 x 41-3/8 x 13 (+1-3/16)
140 (309)
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp. x 1
MITSUBISHI ELECTRIC CORPORATION
Inverter
5.5
-
FV50S
140
2333
4943
0 Pa
Propeller fan x 2
DC-control, Direct-driven by motor
0.15+0.15
HIC circuit
Over-heat protection, Over-current protection
Over-heat protection, Voltage protection
Auto-defrost mode (Reversed refrigerant circle)
R410A x 7.3kg (17 lbs)
LEV circuit
YKM-BK01-J769
YKM-BH79-B678
RC_VBN-11Q067
Installation Manual
Grounded lead wire x 2
Joint: CMY-Y62-G-E
Header:CMY-Y64/68-G-E
Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm
= m
lbs
= kg / 0.4536
*Above specification data is
subject to rounding variation.
C7-R Rev.
3
/min x 35.31
2 - 7