1. SPECIFICATIONS
Model
Power source
Cooling capacity
(Nominal)
*2 Power input
*2 Current input
Heating capacity
(Nominal)
*2 Power input
*2 Current input
External finish
External dimension HxWxD
Net weight
Heat exchanger
FAN
Type x Quantity
*4 External static press.
Motor Type
Motor output
Driving mechanism
Air flow rate
Sound pressure level (measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Liquid (R410A)
Diameter of refrigerant
pipe
Gas (R410A)
Field drain pipe size
Drawing
External
Wiring
Refrigerant cycle
Standard attachment
Document
Accessory
Optional parts
Drain pump
Remarks
Notes :
1.Nominal cooling conditions
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable range of air flow rate.
PEFY-P50VMM-E-S
1-phase 220-240V
50Hz
*1 kW
5.6
*1 kcal / h
4,800
*1 BTU / h
19,100
kW
0.13
A
0.6
*3 kW
6.3
*3 kcal / h
5,400
*3 BTU / h
21,500
kW
0.13
A
0.6
Galvanized steel plate
mm
295 x 935 x 700
inch
11-5/8 x 36-13/16 x 27-9/16
kg(lbs)
33(73)
Cross fin(Aluminum fin and
copper tube)
Sirocco fan x 2
Pa
<30> - 50 - <100>
mmH
O
<3.1> - 5.1 - <10.2>
2
1-phase induction motor
kW
0.075
Direct-driven by motor
(Low-Mid-High)
3
m
/ min
12.0 - 14.5 - 17.0
L/s
200 - 242 - 283
cfm
424 - 512 - 600
(Low-Mid-High)
*2 dB <A>
31-35-38
Polyethylene foam
PP honeycomb fabric.
Fuse
LEV
R410A CITY MULTI
mm(in.)
6.35(1/4) Flare
mm(in.)
12.7(1/2) Flare
Socket (R1) + R1(PT1)
mm(in.)
[O.D.34(1-11/32)]
W661172
W660140
-
Installation Manual, Instruc-
tion Book
Insulation pipe for refrigerant
pipe, Tie band
PAC-KE04DMC-F
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
When the bottom inlet is used, the noise pressure level is 5 to 10 dB greater than when the rear inlet is used.
Take appropriate noise reduction measures on site when using the bottom inlet.
INDOOR UNITS
PEFY-P63VMM-E-S
PEFY-P71VMM-E-S
1-phase 220-240V
1-phase 220-240V
50Hz
50Hz
7.1
6,100
6,900
24,200
27,300
0.14
0.64
8.0
6,900
7,700
27,300
30,700
0.14
0.64
Galvanized steel plate
Galvanized steel plate
295 x 1,175 x 700
295 x 1,175 x 700
11-5/8 x 46-5/16 x 27-9/16
11-5/8 x 46-5/16 x 27-9/16
42(93)
42(93)
Cross fin(Aluminum fin and
Cross fin(Aluminum fin and
copper tube)
copper tube)
Sirocco fan x 2
Sirocco fan x 2
<30> - 50 - <100>
<30> - 50 - <100>
<3.1> - 5.1 - <10.2>
<3.1> - 5.1 - <10.2>
1-phase induction motor
1-phase induction motor
0.078
0.078
Direct-driven by motor
Direct-driven by motor
(Low-Mid-High)
(Low-Mid-High)
13.5 - 16.2 - 19.0
14.5 - 18.0 - 21.0
225 - 270 - 317
242 - 300 - 350
477 - 572 - 671
512 - 636 - 742
(Low-Mid-High)
(Low-Mid-High)
31-35-38
36-40-42
Polyethylene foam
Polyethylene foam
PP honeycomb fabric.
PP honeycomb fabric.
Fuse
Fuse
LEV
R410A CITY MULTI
R410A CITY MULTI
9.52(3/8) Flare
9.52(3/8) Flare
15.88(5/8) Flare
15.88(5/8) Flare
Socket (R1) + R1(PT1)
Socket (R1) + R1(PT1)
[O.D.34(1-11/32)]
[O.D.34(1-11/32)]
W661172
W661172
W660140
W660140
-
Installation Manual, Instruc-
Installation Manual, Instruc-
tion Book
tion Book
Insulation pipe for refrigerant
Insulation pipe for refrigerant
pipe, Tie band
pipe, Tie band
PAC-KE04DMC-F
PAC-KE04DMC-F
C7-R Rev.
PEFY-P80VMM-E-S
1-phase 220-240V
50Hz
8.0
9.0
7,700
30,700
0.2
0.2
0.92
0.92
9.0
10.0
8,600
34,100
0.2
0.2
0.92
0.92
Galvanized steel plate
295 x 1,175 x 700
11-5/8 x 46-5/16 x 27-9/16
42(93)
Cross fin(Aluminum fin and
copper tube)
Sirocco fan x 2
<30> - 50 - <100>
<3.1> - 5.1 - <10.2>
1-phase induction motor
0.078
Direct-driven by motor
(Low-Mid-High)
14.5 - 18.0 - 21.0
242 - 300 - 350
512 - 636 - 742
(Low-Mid-High)
36-40-42
Polyethylene foam
PP honeycomb fabric.
Fuse
LEV
LEV
R410A CITY MULTI
9.52(3/8) Flare
15.88(5/8) Flare
Socket (R1) + R1(PT1)
[O.D.34(1-11/32)]
W661172
W660140
-
-
Installation Manual, Instruc-
tion Book
Insulation pipe for refrigerant
pipe, Tie band
PAC-KE04DMC-F
Unit converter
kcal
=kW x 860
BTU/h =kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg / 0.4536
*Above specification data is