6. CAPACITY TABLES

6-4. Correction at frost and defrost

Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be
calculated by multiplying the correction factor shown in the table below.
Table of correction factor at frost and defrost
Outdoor inlet air temp. °C
Outdoor inlet air temp. °F
PUHY-P300YRJC-A
PUHY-P350YRJC-A
PUHY-P400YRJC-A
PUHY-P450YRJC-A
6-5. Operation temperature range
86
30
77
25
68
20
59
15
50
10
41
5
-20
-15
-4
86
30
77
25
68
20
59
15
50
10
41
5
-20
-15
-4
6
4
2
43
39
36
1.00
0.95
0.84
1.00
0.93
0.82
1.00
0.95
0.90
1.00
0.98
0.89
-10
-5
0
5
10
5
14
23
32
41
50
Outdoor temperature
-10
-5
0
5
10
5
14
23
32
41
50
Outdoor temperature
OUTDOOR UNITS
1
0
-2
-4
34
32
28
25
0.825
0.83
0.87
0.90
0.80
0.82
0.86
0.90
0.87
0.88
0.89
0.90
0.87
0.89
0.90
0.92
15
20
25
30
35
59
68
77
86
95
15
20
25
30
35
59
68
77
86
95
-6
-8
-10
21
18
14
0.95
0.95
0.95
0.90
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
40
45
50
104
113
122
40
45
50
104
113
122
C7-R Rev.
-20
-4
0.95
0.95
0.95
0.95
2 - 48