10. M-NET CONTROL
10-2. Transmission cable specifications
Type of cable
Cable size
Remarks
*1 To wire PAR-CT01MAU, PAR-40MAAU, and PAC-YT53CRAU, use a wire
with a diameter of 0.3 mm
M-P0855
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25
[AWG16]
2
[AWG22]
(L
)
i
ME Remote controller cables
Sheathed 2-core cable (unshielded)
CVV
2
0.3 1.25
[AWG22 16]
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
CVVS, MVVS: PVC insulated PVC sheathed shielded control cable
CPEVS: PE insulated PVC sheathed shielded communication cable
CVV: PVC insulated PVC sheathed control cable
S-Series
MA Remote controller cables
2
[AWG22 16] *1
0.3 1.25
Max length : 200m [656ft]
39