Measuring For Excessive Voltage Drop; Troubleshooting Potential Relay; Troubleshooting Start Capacitor (Black Plastic Casing); Troubleshooting Run Capacitor (Metal Casing) - Traulsen G Series Service Manual

Reach-in & pass thru refrigerator & freezer
Hide thumbs Also See for G Series:
Table of Contents

Advertisement

6.2.7

Measuring for Excessive Voltage Drop:

Now that the compressor has cooled down, measure the voltage supplied to the cabinet while the compressor
is trying to start. If the voltage drops below 104 volts, you may have a problem with the power supply, try a
different circuit.

6.2.8 Troubleshooting Potential Relay:

Disconnect power supply, remove wires and measure for continuity between pins 1 & 2 (Normally Closed
Contacts) of Potential Relay. If continuity is not detected replace potential relay. See Table 14 for part number.
Clamp amp probe onto blue wire connected to pin number 1 of the Potential Relay. Apply power and measure
the current. If the current does not drop out after compressor starts, then the contacts between pins 1 and 2
are stuck in the closed position. In this case the potential relay must be replaced. See Table 14 for part number.

6.2.9 Troubleshooting Start Capacitor (Black Plastic Casing):

If the voltage measures 115 Volts +/- 10% but the compressor doesn't start, measure the current with your amp
meter at the common terminal of the compressor. If the current spikes very high but the compressor doesn't
start, disconnect power so that you can remove all the start components for testing. Start capacitors can be
tested with a microfarad tester. For the most accurate measurement remove the resistor from the start
capacitor. (The start capacitor should never be used without the resistor as this will damage the start relay.)
If microfarads measured do not match values in table below, replace start capacitor. See Table 13 for specs and
part number for start capacitor.

6.2.10 Troubleshooting Run Capacitor (Metal Casing):

If the compressor starts and runs with an amp draw higher than the RLA and the compressor is a capacitance
run compressor (which means it requires a run capacitor), disconnect power so that you can remove the run
capacitor from the circuit for testing with a microfarad tester. Connect the microfarad tester across both
terminals of the run capacitor. See Table 13 for specs and part numbers for run capacitors. If the microfarads
measured do not match specs given, replace the run capacitor.
Note: If the run capacitor is swollen or leaking fluid, replace run capacitor.
Figure 51: Potential Relay Schematic
52

Advertisement

Table of Contents
loading

Table of Contents