6. Troubleshooting
6.1
Condensate Overflow Troubleshooting
6.1.1 Condensate Overflow:
The condensate pan generally does not overflow unless there is an excess of ambient air infiltrating the
cabinet.
• Hump Cover not Sealed Properly. i.e., torn, or missing Foam Tape
• The door is not sealed properly.
• Door not self-closing (see door section)
• Putty not fully sealing refrigeration lines penetrating evaporator compartment.
• On refrigerators with electric defrost shorting the time between defrost may help to reduce the
amount of water (see control section)
Figure 46: Troubleshooting Condensate Pan Overflow