3.9 I Limit, OCP Delay

I Limit represents Current Limit, it is used to set the maximum sum current (rms) for
two phase. Its range is related to Voltage Level setting:
OCP Delay represents Over Current Protection (OCP) Delay Time, it is the delay time
to shut down output voltage after output current reaches OCP point (I Limit). Its range is
between 0~9 seconds, resolution is 0.1 second. Both I Limit and OCP Delay are controlled
by FW instead of by HW.
Operation of OCP Delay Time: When output current (rms) measurement is over I Limit
parameter, OCP delay time start to count. If OCP last t seconds, then:
 t > OCP Delay parameter  Output open, display Software OCP.
 t < OCP Delay  Output continues, no protections or reports.
Operation for ILimit is 3A, OCP delay time is 1.5 shows as above:
1. Press
29
│ www.deltaww.com
Voltage Level
300V
150V
or
to move cursor to I Limit
I Limit
0.0~32.0 A
0.0~64.0 A