5.
Equipment
5-1. Three-phase and single-phase simultaneously Output
This generator is capable of generating three-phase and single-phase three-wire output
simultaneously. (Three-phase output terminal and single-phase three-wire output terminal are
equipped individually.)
Neither switching operation of output nor switching operation of wiring is needed.
Three-Phase and Single-Phase Three-Wire Output Terminal
L1
< NOTE >
Refer to section "7-2. Connecting Load Cables" for Load Connections.
If using three-phase output simultaneously with a single-phase three-wire type output, use
in a range where the total current does not exceed the rated current.
5-2. Available Output Monitor
The available generated output for each output power source is displayed digitally. You can
use the display selector switch to change the display in the following order: three-phase,
single-phase three-wire U-W output, and single-phase three-wire U-N output. Three-phase
output is constantly displayed when the engine is stopped.
< NOTE >
Consider the digitally displayed available output as an
approximate estimate. Be especially sure to thoroughly
consider the displayed value and the used load capacity when
using a load such as that of a motor with a large starting
capacity.
The displayed output capacity might not be correct values if
using a four-wire connection (single-phase using the N
terminal) for a three-phase output power source. Connect to a
single-phase/three-line type power source if using a
single-phase power source.
If "- -" is displayed for the available output, it means that usage
has exceeded the rated capacity. Immediately stop the equipment being used and reduce the
load capacity of the equipment.
5-3. Warning Indicators
WARNING : INJURY
Do not open the check door during operation. Be careful of pinching or
catching of moving parts such as the cooling fan and fan belt.
Always be sure to stop the engine and remove the engine key when
performing inspection or maintenance.
L2
L3
N
GROUND
9
U
W
Display Selector
Switch